Electrical Data - Ingersoll Rand IRN 15 HP Manuel D'utilisation Et D'entretien

Masquer les pouces Voir aussi pour IRN 15 HP:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

24
INSTALLATION / HANDLING
ELECTRICAL DATA − ALL UNITS IRN 20HP / 15kW
Standard voltage
Drive motor
Motor enclosure
Power
Full load current (maximum)
Starts per hour (maximum)

ELECTRICAL DATA

Control voltage
Maximum fuse rating
See note 1, 3
Minimum wire size AWG
2
(mm
)
See note 2, 3
ELECTRICAL DATA − ALL UNITS IRN 25HP / 18.5kW
Standard voltage
Drive motor
Motor enclosure
Power
Full load current (maximum)
Starts per hour (maximum)
ELECTRICAL DATA
Control voltage
Maximum fuse rating
See note 1, 3
Minimum wire size AWG
2
(mm
)
See note 2, 3
1. The correct type and rating of line input fuse MUST BE fitted onto
the customers isolator or breaker close to the compressor.
Fast Acting Class−J, T or Semiconductor type, Current limiting,
Interrupt Rating − 200,000 Amps RMS SYM.
Alternate fuse may be used if the time current characteristics are faster
than fuses recommended in this section.
2. PVC/PVC Type Calculated using the following conditions:
i) PVC insulated cable, armoured, copper conductors.
ii) Cable clipped to a wall, in free air.
iii) Ambient temperature of 40_C (104_F) and relative humidity of 40%.
iv) 20m (65ft) cable run.
v) Volt drop limited to −10% during starting, −4% during normal
running.
vi) Protected by the fuse listed above.
3. Always apply local electrical codes for sizing cables and fusing.
en
Low Voltage
208V
230V
58.3
52.7
100A
90A
4 (25)
4 (25)
Low Voltage
208V
230V
73.2A
63.7A
125A
100A
3 (35)
4 (25)
High Voltage
380V
IP65
20HP / 15kW
31.9
20
24VDC
50A
8 (10)
High Voltage
380V
IP65
25HP / 18.5kW
40.2A
20
24VDC
70A
6 (16)
If there are any deviations from the above, or special regulations
apply, the installation must be planned by a competent, qualified
engineer.
NOTE
All data applies to standard product only.
400V
460V
30.3
26.3
50A
45A
8 (10)
8 (10)
400V
460V
38.2A
33.2A
60A
50A
6 (16)
8 (10)
http://air.ingersollrand.com

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Irn 20 hpIrn 25 hpIrn 22 hpIrn 30 hpIrn 40 hp

Table des Matières