Commissioning

Possible settings via DIP switch

The front panel DIP switches serve to set:
ƒ The node address (switches 1 ... 7)
ƒ The baud rate (switches 8 ... 10)
The Lenze setting of all DIP switches is OFF.
)
Note!
Settings via codes
In the Lenze setting ˘ Address switches 1 ... 7 = OFF ˘, the values are
ƒ
accepted from the codes C1850/C2350 (node address) and C1851/C2351
(baud rate).
– Node addresses > 99 can only be set via DIP switch.
– The baud rates 10 kbps and 20 kbps can only be selected via DIP switch.
Writing the codes (e.g. with GDC via CAN) has a direct effect on the
ƒ
standard device codes C0009 and C0126.
Acceptance of code changes by:
ƒ
– Switching off and then on again the voltage supply;
– "Reset node" with C0358 = 1;
– Network management command "Reset Communication";
– Set C2120 (AIF control byte) = 1.
The codes are inactive if at least one address switch (1 ... 7) has been set to
ƒ
ON position before a renewed mains connection.