Bus cable length
)
Note!
It is absolutely necessary to comply with the permissible cable lengths.
ƒ
If the total cable lengths of the CAN nodes differ for the same baud rate,
ƒ
the smaller value must be used to determine the max. cable length.
Observe the reduction of the total cable length due to the signal delay of
ƒ
the repeater.
Total cable length
The baud rate determines the total cable length.
Baud rate [kbps]
10
20
50
125
250
500
1000
Tab. 1
Total cable length
EDKMF2178IB DE/EN/FR 6.1
Electrical installation
Wiring of system bus (CAN)
Max. bus length [m]
7450
3950
1550
630
290
120
25