elco AEROTOP SPLIT M-RX Guide D'installation page 91

Table des Matières
Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 150
Setting
DESCRIPTION
17
2
2
ECO / COMFORT
17
2
3
FlowT HP Off set
17
2
4
Boost Time
17
2
5
External temperature correction
17
2
6
Active Resistance Stages
17
2
7
Pro-Tech anode active
17
2
9
Antiblocking pump enable
17
3
Central Heating
17
3
0
CH pump prerun time
17
3
1
Time for prerun new attempt
17
3
2
CH Pump Overrun
17
3
3
Pump Speed Control
17
3
4
Delta T Pump Setpoint
17
3
7
Max PWM Pump
17
3
8
Min PWM Pump
17
3
9
Floor drying Flow Set Point T
17
4
Cooling
17
4
0
Cooling mode activation
17
4
1
Cooling anticycling time
17
4
2
DeltaT_HP_Flow_Comp
17
5
Domestic Hot Water
17
5
0
DHW Comfort Setpoint T
17
5
1
DHW Reduced Set Point T
17
5
2
Comfort Function
17
5
3
Max HP charging time
17
5
5
Antilegionella start time [hh:mm]
17
5
6
Thermal Cleance Cycle frequency
17
6
Manual Mode - 1
17
6
0
Manual mode activation
17
6
1
HP circulator control
17
6
2
Diverter valve control
RANGE
Eco Plus
Eco
Average
Comfort
Comfort Plus
0 ÷10°C
0 ÷ 60 min
- 3; + 3°C
1 Stage
2 Stages
3 Stages
OFF - ON
OFF - ON
30 ÷ 255 sec.
0 ÷ 100 sec.
0 ÷ 16 min.
Low speed
High speed
Modulating
5 ÷ 20°C
PWM Min-100
20%-PWMmax
25 ÷ 60°C
Cooling not active
Cooling active
0 -10 min.
-10 ÷ 0°C
35 ÷ 65°C
35°C - Par. 15.5.0
Disabled
Time based
Always Active
HC-HP
HC-HP 40°C
Green Mode
30 ÷ 240 min.
[00:00-24:00]
1 ÷ 30 days
OFF - ON
OFF
Low Speed
High Speed
DHW
CH
DEFAULT
Average
2°C
16 min.
0°C
2 Stages
OFF
ON
30 sec.
90 sec.
3 min.
Modulating
5°C
100
40%
55°C
Cooling not active
0 min.
0°C
55°C
35°C
Green Mode
120 min.
01:00
30 days
OFF
OFF
DHW
91 / GB
Table des Matières