Setting

Setting of parameters

WARNING
To guarantee safety and correct opera-
tion of the system interface, it must be
commissioned by a qualifi ed technician
in possession of the skills as required by
law.
Ignition procedure
- Insert the system interface into the
connection shoe by pushing it gently
downwards; after a brief initialisation,
the system interface will be con-
nected.
- The display screen shows "Select lan-
guage". Turn the knob and select the
desired language. Press the OK button
to confi rm.
- The display shows date and time.
Use the knob to select the date, press
the OK button, turn the knob to select
the exact day, press the OK button to
confi rm and move on to the month,
followed by the year, pressing the OK
button to confi rm after each step. Turn
the knob to select the time, press the
OK button, turn the knob to select the
exact hour, press the OK button to
confi rm and move on to the minute
value. Press the OK button to confi rm.
Turn the knob and select summer
time, press the OK button, select auto
or manual, press the OK button.
The display shows the basic screen.
- Select the country
Now follow step by step directions
that appear from time to time on the
display.
Technical Area access
- Simultaneously press the back "
"and "OK" buttons until "Insert code"
appears on the display.
- Turn the knob to enter the technical
code (234) then press OK; the display
will show TECHNICAL AREA:
- Language, date and time
- BridgeNet Bus network settings
- Complete menu
- Confi guration Wizard
- Service
- Faults
Turn the knob and select:
- BridgeNet Bus network settings
The display will show the list of devices
connected within the system:
- System interface (local)
- Energy Manager
- Zone Manager
To set the correct zone to which the
system interface is associated, turn the
knob and select:
- System interface (local)
Press the OK button.
Turn the knob and set the correct zone.
Press OK to confi rm the setting.
Turn the knob and select:
- COMPLETE MENU
Press the OK button to confi rm.
Turn the knob and select:
17.0
USER PARAMETERS
Press the OK button to confi rm.
Turn the knob and select:
17.0.0 CH mode
Press the OK button to confi rm.
Turn the knob and select:
- 0. Green
(excludes the electric resistances for
the integration of the heating)
- 1.Standard
Press the OK button to confi rm.
Turn the knob and select:
17.0.1 Quiet Mode Activation
Press the OK button to confi rm.
Turn the knob and select:
- ON (active function to reduce noise)
- OFF
Press the OK button to confi rm.
Turn the knob and select:
17.0.4 Domestic Hot Water BOOST
Press the OK button to confi rm.
Turn the knob and select:
- ON (enable the boost cycle to speed
up the DHW service. Max duration 180
min.)
- OFF
17.0.5 Delta T PV sanitary setpoint
Press the OK button.
Turn the knob to set the value that in-
creases the sanitary setpoint when the
PV contact is supplied.
Turn the knob and select:
17.1
EM INPUT OUTPUT
CONFIGURATION
Press the OK button to confi rm.
Turn the knob and select:
17.1.0 HV Input 1
- 0. Not defi ned: no function associated
to the input. Fault 941 is displayed.
- 1. Absent: Input not enabled.
- 2. EDF (night tariff ): Input not acti-
ve (0V). If the Comfort function (par
.17.5.2) is set as HC-HP the heat pump
and the heating resistors tank charge
is suspended; if the comfort function
is set as HC-HP 40°C, the tank charge is
limited, considering as DHW setpoint
temperature the minimum between
the reduced setpoint temperature
and 40°C.
Inut active (230V). The heat pump and
the resistors are enabled for the tank
charge following the standard logics.
- 3. SG Ready 1: input signal nr 1 for the
SG Ready standard (see. Paragraph
SMART GRID READY STANDARD)
- 4. External Switch OFF signal: input si-
gnal to set the the machine OFF. Every
heat request, cooling request and DHW
service is stopped and antifreeze pro-
tection logics are active
Push OK button.
Turn the knob and select:
17.1.1 HV Input 2
- 0. Not defi ned: no function associated
to the input. Fault 942 is displayed.
- 1. Absent: Input not enabled.
- 2. DLSG (load shedding): Input not
active (0V). Heating resistors are di-
sabled in every cycles.
- 3. SG Ready 2: input signal nr 2 for the
SG Ready standard (see. Paragraph
SMART GRID READY STANDARD)
- 4. External Switch OFF signal: input si-
gnal to set the the machine OFF. Every
heat request, cooling request and DHW
service is stopped and antifreeze pro-
tection logics are active
17.1.2 HV Input 3
- 0. Not active
- 1. PV integration active: Input not acti-
ve (0V), no tank integration from PV
system. Input active (230V): if the sy-
stem is in stand-by, the DHW setpoint
temperature is incremented by the
amount defi ned by the parameter
17.0.5 - PV Delta T DHW setpoint temp.
17.1.3 AUX Input 1
- 0. None
- 1. Humidistat: when the contact is clo-
sed, the heat pump switches off
17.1.4 AUX Output 1 (AFR)
- 0. None
- 1. Fault alarm: the contact is closed in
case of fault