Setting
17.8.5 Refrigerante Recover Cycle
Activate this function to recover the re-
frigerant gas before every maintenance
operation on the refrigerant circuit.
17.8.6 Resistance Power Rating Confi -
guration
set the backup resistance confi guration
- 0: if the backup interface module com-
prizes 2kW+2kW (+2kW) electrical resi-
stances
- 1: if the backup interface module com-
prizes 2kW+4kW electrical resistances
17.8.7 Defrost
Test the defrost function ON
17.8.8 TDM Flow Sensor Type.
Set the fl ow sensor relf recognition or
fl ow meter type DN15.
Turn the knob and select:
17.9
ENERGY MANAGER STATISTICS
17.10
HP DIAGNOSTICS - 1
17.11
HP DIAGNOSTICS - 2
17.12
HP DIAGNOSTICS - 3
17.13
HP DIAGNOSTICS - 4
Displays the characteristic information
of the heat pump (temperatures, water
fl ow switch status, HP status, etc).
Smart grid ready standard
The operation mode of the system according to the the Smart Grid Protocol is reported in the table below.
SG Ready 1
SG Ready 2
Input Status
Input Status
0 V
0V
230V
0V
0
230V
230V
230V
84 / GB
Turn the knob and select:
17.14 ENERGY MANAGER
DIAGNOSTICS -1 Input
Displays the values of the system board
inputs
Turn the knob and select:
17.15 ENERGY MANAGER
DIAGNOSTICs - 2 Output
Displays the values of the system board
outputs
Turn the knob and select:
17.16
ERROR HISTORY
Last 10 Errors.
Turn the knob and select:
17.17
RESET MENU
Reset Factory Settings.
Description
The system works according to the standard logics
The system is off for maximum 2 hours, but antifreeze protection is active
In time program mode the Reduced Setpoint Temp is increased to the Comfort Setpoint
temp. Heating resistors are OFF
In time program mode the Reduced Setpoint Temp is increased to the Comfort Setpoint
temp. Heating resistors are enabled