Operating area

For proper functioning and a good temperature distribution, the stove shoul be positioned in a location
where it is able to take in the air necessary for combustion of the pellet (about 40 m3/h must be available,
as laid down in the standard governing the installation and in accordance with local national standards).
The volume of the room must not be less than 30 m
openings made in walls (in proximity to the stove) which give onto the outside, with a minimum cross-
section area of 100 cm
to be obstructed in any way. Alternatively, the air can be taken from rooms adjacent to the one which
needs ventilating, as long as they are provided with an air intake from the outside, and are not used
as bedrooms or bathrooms, and provided there is no fi e risk such as there is for example in garages,
woodsheds, and storerooms, with particular reference to what is laid down in current standards.
It is not permissible to install the stove in bedrooms, bathrooms, or in a room
where another heating appliance is installed (fireplace, stove etc.) which does
not have its own independent air intake.
Locating the stove in a room with an explosive atmosphere is prohibited.
The floor of the room where the stove is to be installed must be strong enough to take its
weight. If walls are flammable, maintain a minimum distance of 40 cm at the rear (A), of 40
cm at the side (B) and 100 cm at the front. If the room contains objects which are believed
to be particularly delicate, such as drapes, sofas and other furniture, their distance from
the stove should be considerably increased. The two side walls of the stove must be acces-
sible for maintenance by authorized technicians.
In the presence of wood floors, install a floor protection surface in compliance
with the rules in force in the country
Connection to the external air intake
It is essential that at least as much air must be able
to flow into the room where the stove is installed
as is required for proper combustion in the applian-
ce and for the ventilation of the room. This can be
effected by means of permanent openings in the
walls of the room to be ventilated, which give onto
the outside, or by single or collective ventilation
ducts.
For this purpose, on the external wall near the
stove, a hole must be made with a minimum free
cross-section of 100 cm
hole of 12 cm diameter or a square hole 10x10
cm) protected by a grille on the inside and the out-
side.
The air intake must also:
• communicate directly with the room where the
stove is installed
• be protected by a grille, metal mesh or suitable
guard, as long as this does not reduce the area
below the minimum.
• positioned in such a way as to be impossible to
obstruct.
55
. These openings must be made in such a way that it is not possible for then
2
. (equivalent to a round
2
. The air must come in through permanent
3
40 cm (A)
Min.
100
cm
2

Publicité