Safety instructions
Residual hazards
ƒ If you use the "flying−restart circuit" function (C0142 = 2, 3) for machines with a
low moment of inertia and minimum friction:
– After controller enable has been effected in the standstill status, the motor may
temporarily start up, or change direction of rotation.
ƒ The motec heatsink has an operating temperature > 60 °C:
– Direct skin contact with the heatsink results in burns.
Device protection
ƒ Frequent switching of the supply voltage (e.g. inching mode via mains contactor)
can overload and destroy the input current limitation of the controller:
– Wait for at least 3 minutes between two starting operations.
ƒ Only switch contactors in the motor cable when the controller is inhibited.
Otherwise ...
– monitoring functions of the controller can be activated.
– the controller can be destroyed under unfavourable operating conditions.
Motor protection
ƒ
For some controller settings, the connected motor may overheat (e.g. when
operating the DC injection brake or a self−ventilated motor at low speed for longer
periods).
– Using an overcurrent relay or a temperature monitoring device provides a large
degree of protection against overload.
– We recommend to use PTC thermistors or thermal contacts for motor
temperature monitoring. (Lenze three−phase AC motors are equipped with
thermal contacts (NC contacts) as standard)
– PTC thermistors or thermal contacts can be connected to the controller.
Protection of the machine/system
ƒ Drives can attain dangerous overspeeds (e.g. setting of high output frequencies
with motors and machines not qualified for this purpose).
– The controllers do not offer any protection against these operating conditions.
Use additional components for this purpose.
84