Troubleshooting and fault elimination
Fault messages
1)
Keypad
PC
67
ce6
a
68
ce7
a
91
EEr
a
ErP0
...
ErP19
a
95
FAn1
a
FAn1
105
H05
a
140
id1
a
32
LP1
a
182
LP1
134
Fault
Cause
System bus
CAN controller reports
(CAN) function
"Warning" or "BUS−OFF"
module on FIF
status
has the
"Warning" or
"BUS−OFF"
status
(configurable in
C0126)
Communication
Node does not respond or is
error during
not available
remote
parameterisatio
n via system bus
(C0370)
(configurable in
For operation with
C0126)
application I/O:
Parameter set change−over
has been parameterised
incorrectly
External fault
A digital signal assigned to
(TRIP−SET)
the TRIP−Set function is
activated
Communication
Various
abort between
keypad and
standard device
Fan failure
Fan is defective
(only 8200
motec
3 ... 7.5 kW)
Fan is not connected
TRIP or warning
configurable in
C0608
Internal fault
Faulty parameter
Motor is not connected
identification
l
Failure of one/several
Motor phase
motor phases
error
(display when
l
Motor current is too low
C0597 = 1)
Motor phase
error
(Display when
C0597 = 2)
l
Remedy
l
Check bus termination
l
Check shield connection of
the cables
l
Check PE connection
l
Check bus load, reduce the
baud rate, if necessary
l
Check bus termination
l
Check shield connection of
the cables
l
Check PE connection
l
Check bus load, reduce the
baud rate, if necessary
The "parameter set
change−over" signal (C0410/13,
C0410/14) must be connected
to the same source in all
paramerter sets
Check external encoder
Contact Lenze
Replace fan
Connect fan
Check wiring
Contact Lenze
Connect motor
l
Check motor supply cables
l
Check V
boost,
min
l
Connect motor with a
corresponding power or
adapt motor with C0599
EDK82MV222 DE/EN/FR 11.0