Troubleshooting and fault elimination
Fault messages
1)
Keypad
PC
53
OH3
a
54
OH4
a
203
OH51
OU
c
22
OUE
a
75
Pr
a
72
Pr1
a
73
Pr2
a
77
Pr3
a
78
Pr4
a
136
Fault
Cause
PTC monitoring
Motor too hot due to
(TRIP)
impermissible high currents
or frequent and too long
(display when
acceleration processes
C0119 = 1 or 4)
No PTC connected
Controller
Controller is too hot inside
overtemperature
PTC monitoring
Motor too hot due to
impermissible high currents
(display when
or frequent and too long
C0119 = 2 or 5)
acceleration processes
No PTC connected
DC−bus
Mains voltage is too high
overvoltage
(message or TRIP
configurable in
Braking operation
C0310)
Earth leakage at motor end
Faulty parameter
All parameter sets are
transfer via
defective
keypad
Faulty PAR1
Parameter set 1 is defective
transfer via
keypad
Faulty PAR2
Parameter set 2 is defective
transfer via
keypad
Faulty PAR3
Parameter set 3 is defective
transfer via
keypad
Faulty PAR4
Parameter set 4 is defective
transfer via
keypad
l
Remedy
Check drive dimensioning
Connect PTC or switch off
monitoring
l
Reduce controller load
l
Improve cooling
l
Check fan in the controller
Check drive dimensioning
Connect PTC or switch off
monitoring
Check supply voltage
l
Increase deceleration times
l
For operation with an
external brake resistor:
– Check dimensioning,
connection and supply
cable of the brake resistor
– Increase deceleration
times
Check motor supply cable and
motor for earth fault
(disconnect motor from the
inverter)
Before enabling the controller,
repeat the data transfer or load
the Lenze setting
EDK82MV222 DE/EN/FR 11.0