Commissioning
Important controller codes
Code
No.
Name
C0148
Identifying
*
motor data
s
C0517
User menu
*
v
1 Memory 1
2 Memory 2
3 Memory 3
4 Memory 4
5 Memory 5
6 Memory 6
7 Memory 7
8 Memory 8
9 Memory 9
10 Memory 10
128
Possible settings
Lenze
Selection
0
0
Ready
1
Start identification
l
V/f rated frequency (C0015),
slip compensation (C0021)
and motor stator inductance
(C0092) are calculated and
saved
l
The motor stator resistance
(C0084) = total resistance of
the motor cable and motor is
measured and saved
50
C0050 Output frequency
(MCTRL1−NOUT)
34
C0034 Range of analog setpoint
selection
7
C0007 Fixed configuration of digital
input signals
10
C0010 Minimum output frequency
11
C0011 Maximum output frequency
12
C0012 Acceleration time main setpoint
13
C0013 Deceleration time main setpoint
15
C0015 V/f rated frequency
16
C0016 V
boost
min
2
C0002 Parameter set transfer
Possible entries for C0517
xxxx
All codes apart from the codes
labelled with "(A)".
l
IMPORTANT
Only when the motor is cold!
1. Inhibit controller, wait
until drive is at standstill
2. Enter the correct values
from the motor
nameplate in C0087,
C0088, C0089, C0090,
C0091
3. Set C0148 = 1, confirm
with v
4. Enable controller:
The identification
– starts, c goes out
– the motor "whistles"
faintly but it does not
rotate!
– takes approx. 30 s
– is completed when c
is lit again
5. Inhibit controller
l
After mains switching or
in the g function the
code from C0517/1 is
displayed.
l
In the Lenze setting the
user menu contains the
most important codes for
commissioning the
operating mode "V/f
characteristic control with
a linear characteristic"
l
If the password protection
is active, only the codes
entered in C0517 can be
freely accessed
l
If less than 10 codes are
required, assign the value
"0" (zero) to the memory
locations not used. Please
observe that the software
automatically assigns
code C0050 to a memory
location that is not used, if
it has not been explicitly
assigned to another
memory location.
Syntax:
Codes: C0517/x = cccc
Subcodes: C0517/x = cccc.ss