Commissioning
Vector control
Switch−on sequence
16.
Start the motor parameter identification (C0148)
A
Ensure that the controller is inhibited
B
Set C0148 = 1
C
Enable the controller
If segment c becomes active again after approx. 30
D
s, inhibit controller again.
17.
If necessary, select more parameters
18.
Go to the menu ALL
A Check the fan monitoring setting under code
C0608:
– for 8200 motec 0.25...0.37 kW and 0.55...2.2
kW:
C0608 = 0! (default setting)
– for 8200 motec 3...7.5 kW:
C0608 =1 (recommended) or C0608 = 2!
Stop!
Function must be activated during
commissioning! Otherwise, the controller may
be destroyed through overheating!
– for all other controllers:
C0608 = 0 ! (default setting)
B Select additional functions via codes, if necessary.
When all settings are complete:
19.
Select setpoint
20.
Enable the controller
21.
The drive is now running.
116
Comment
Only when the motor is cold!
Terminal X3/28 = LOW
Pressv
l
Terminal X3/28 = HIGH
l
The identification starts:
– Segment c is off
– The motor consumes current and
– The motor does not rotate!
l
Terminal X3/28 = LOW
l
Identification is completed.
l
Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance (C0092)
l
Measured and stored:
– Motor stator resistance (C0084) =
Activate e.g. JOG frequencies (C0037,
C0038, C0039) or motor temperature
monitoring (C0119)
E.g. via potentiometer at
terminals 7, 8, 9
Terminal X3/28 = HIGH
If the drive does not start, additionally
press u
l
makes a high−pitched" tone.
Total resistance of motor cable
and motor
EDK82MV222 DE/EN/FR 11.0