Lenze 8200 motec E82MV551_4B Instructions De Montage page 102

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5
Electrical installation
Mains connection
Fuses and cable cross−sections
Type
Mains
E82MV551_4B
3/PE AC
E82MV751_4B
320 ... 550 V;
E82MV152_4B
45 ... 65 Hz
E82MV222_4B
1)
Universal−current sensitive earth−leakage circuit breaker
Observe national and regional regulations
When using earth−leakage circuit breakers, observe the following:
ƒ Earth−leakage circuit breakers must only be installed between mains supply and
controller.
ƒ Earth−leakage circuit breakers can trip incorrectly due to
– capacitive compensation currents of the cable shields during operation
(especially with long, shielded motor cables),
– simultaneous connection of several controllers to the mains supply.
Dimensioning of mains contactors
Type
E82MV551_4B
E82MV751_4B
E82MV152_4B
E82MV222_4B
Observe national and regional regulations
1)
e.g. 3x E82ZJ004 current limiting module
102
Fuse
M6 A
M6 A
M6 A
M10 A
Rated current of mains contactor
With starting current limitation
10 A
Installation acc. to EN 60204−1
Circuit breaker
B6 A
B6 A
B6 A
B10 A
1)
Without starting current limitation
l
FI
L1, L2, L3, PE
2
[mm
]
1
1
³ 30 mA
1
1.5
16 A
20 A
EDK82MV222 DE/EN/FR 11.0