Code
No.
Name
C0088 Rated motor
current
C0089 Rated motor
frequency
C0090 Rated motor
voltage
C0091 Motor cos
C0119
Configura−
v
tion of
motor
temperature
monitoring
(PTC input) /
earth fault
detection
C0140
Additive
*
frequency
setpoint
(NSET1−
NADD)
EDK82MV222 DE/EN/FR 11.0
Possible settings
Lenze
Selection
à
0.0
50
10
à
50
à
0.40
0
0
PTC input
inactive
1
PTC input
active,
TRIP effected
2
PTC input
active,
warning
effected
3
PTC input
inactive
4
PTC input
active,
TRIP effected
5
PTC input
active,
warning
effected
0.00
−650.00
l
Commissioning
Important controller codes
0.1 (A)
650.0
{1 Hz}
960
{1 V}
500
{0.1}
1.0
Earth fault
detection active
Earth fault
detection
inactive
{0.02
650.00
Hz}
IMPORTANT
à
Device−dependent
0.0 ... 2.0 x rated output
current of the controller
à
230 V for 230 V
controllers,
400 V for 400 V controllers
à
Device−dependent
l
Configure signal output in
C0415
l
If several parameter sets
are used, monitoring has
to be set separately for
every parameter set.
l
Deactivate earth fault
detection if the earth fault
detection is actuated
unintentionally.
l
If the earth fault detection
is activated, the motor
starts with a delay of
approx. 40 ms after
controller enable has been
set.
Selection via j function
l
of the keypad or
parameter channel
l
Acts additively on the
main setpoint
l
Value will be stored when
switching the mains or
removing the keypad
l
C0140 is only transferred
during parameter set
transfer with GDC (not
with keypad)
7
127