6.
If you are installing power management software, connect your
computer to one of the communication ports or optional
connectivity card. For the communication ports, use an appropriate
cable as follows:
S
For the AS/400. Use the supplied AS/400 communication cable.
The "AS/400" end of the cable connects to the port marked
"J14" or "UPS"on the AS/400 rear panel.
S
For PCs and workstations. Use the communication cable supplied
with the power management software CD.
7.
If an emergency power-off (disconnect) switch is required by local
codes, see "Remote Emergency Power-off" (REPO) on page 13 to
install the REPO switch before powering on the UPS.
8.
If you are installing EBM(s), continue to the following section,
"Connecting the EBM(s)." Otherwise, continue to "Starting the
UPS" on page 22.

Connecting the EBM(s)

To install the optional EBM(s) for a UPS:
1.
On the rear of the UPS, remove the cable retention clip covering
the battery connector. Retain the clip and screws. See Figure 3.
2.
Installations with one EBM only. Remove the cable retention clip
covering the right battery connector. Retain the clip and screws.
3.
Installations with more than one EBM. For all EBMs except the last
EBM, remove the cable retention clips covering both battery
connectors. Do not remove the clip from the second battery
connector on the last EBM. Retain the clips and screws.
A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and
will not harm personnel. Insert the EBM cable into the UPS battery connector quickly and
firmly.
4.
Plug the EBM cable(s) into the battery connector(s) as shown in
Figure 3. Up to four EBMs may be connected to the UPS.
5.
For each cable retention clip removed, rotate the clip and install it
under each EBM cable connection using the retained screws.