Eaton 9130 Guide D'installation page 15

Pour applications ibm
Masquer les pouces Voir aussi pour 9130:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 61
8.
Press the
The UPS front panel display changes status to "UPS starting..."
9.
Check the UPS front panel display for active alarms or notices.
Resolve any active alarms before continuing. See
"Troubleshooting" in the UPS user's guide.
If the
Check the UPS status from the front panel to view the active
alarms. Correct the alarms and restart if necessary.
10. Verify that the
UPS is operating normally and any loads are powered.
The UPS should be in Normal mode.
11. Press the
12. If optional EBMs are installed, see "Configuring the UPS for EBMs"
on page 24 to set the number of installed EBMs.
13. To change other factory-set defaults, see the "Operation" section.
NOTE IBM recommends setting the date and time.
NOTE At initial startup, the UPS sets system frequency according to input line frequency
(input frequency auto-sensing is enabled by default). After initial startup, auto-sensing is
disabled until manually re-enabled by output frequency setting.
NOTE At initial startup, input voltage auto-sensing is disabled by default. When manually
enabled by output voltage setting, at the next AC startup the UPS sets output voltage
according to input line voltage. After the subsequent startup, auto-sensing is disabled until
manually re-enabled by output voltage setting.
14. If you installed an optional REPO, test the REPO function:
Activate the external REPO switch. Verify the status change on the
UPS display.
Deactivate the external REPO switch and restart the UPS.
EATON 9130 (9910-E15/E16) UPS Installation Guide for IBM
button on the UPS front panel for at least one second.
indicator is on, do not proceed until all alarms are clear.
indicator illuminates solid, indicating that the
ESC
button until the start screen appears.
S
®
Applications
164201783 Rev 2
INSTALLATION
15

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

9910-e1544v6738103007458-39919910-e1644v6739103007459-3991

Table des Matières