Télécharger Imprimer la page

RIB K500 Mode D'emploi page 31

Masquer les pouces Voir aussi pour K500:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

1 - Position DIP 1 to ON and then DIP 3 to ON.
2 - The red programming DL1 LED will flash ON and OFF, one second on each, for 10
seconds.
3 - Press and hold the PROG button for 5 seconds. The green DL2 LED will flash twice to
confirm that the stored codes have been deleted.
4 - The red programming DL1 LED remains active and you can programme new codes as
shown above if required.
5 - Reposition DIP 1 to OFF and DIP 3 to OFF.
6 - You have completed the procedure.
HOW TO CHECK IF THE MEMORY IS FULL FOR RADIO CODES USED ONLY FOR
COMPLETE OPENING
You can only check the memory if the gate is closed.
1 - Position DIP 1 to ON and then DIP 3 to ON.
2 - The green DL2 LED will flash 6 times if the memory is full (30 codes have been stored).
3 - After this, the DL1 programming LED will remain active for 10 seconds, so that you can
delete all codes if required.
4 - Reposition DIP 1 to OFF and DIP 3 to OFF.
5 - You have completed the procedure.
FUNCTIONING OF CONTROL ACCESSORIES
ATTENTION: ONLY IMPULSIVE COMMANDS HAVE TO BE CONNECTED.
Make sure that any other type of command accessories (e.g. mass detectors)
used on the installation are set in the IMPULSIVE mode, otherwise, the gate will
be operated even without the protection of the safety devices.
STEP BY STEP or AUTOMATIC commands
(K BUTT button, PED BUTT button, RADIO REMOTE button)
DIP 6 - ON The K BUTT, the PED BUTT button, the RADIO REMOTE buttons perform the
cyclic command open-stop-close-open-stop-etc.
DIP 6 - OFF The K BUTT, the PED BUTT button, the RADIO REMOTE buttons perform:
- the open command, if pressed with the gate completely closed
- the close command, if pressed with the gate completely opened
- no effect, if pressed during the gate opening
- the gate re-open, if pressed while the gate is closing
The K BUTT opens the gate completely, whereas the PED BUTT opens the gate partially as
described in Point D.
CLOCK FUNCTION
If you want the Clock Function must request K2007 with firmware 12 NOUP.
ATTENTION: A CLOCK CONNECTED TO K2007 with fw 05 or more ACTIVATES THE
AUTOMATIC MOVEMENT OF THE GATE WITHOUT HAVING THE PROTECTION OF
THE SAFETY DEVICES!
The Clock Function is useful during rush hours, when traffic is heavy and the flow is slow (e.g.
entrance/exit of employees, emergencies in residential areas or car parks and, temporarily,
for removal vans) and it's necessary to keep the gate opened.
CLOCK FUNCTION APPLICATION
It is necessary to request a K2007 control panel with firmware 12 NOUP.
Select the automatic functioning DIP 6 OFF.
It can be done by connecting a switch and/or a daily/weekly clock either in parallel to the K
BUTT button or instead of the K BUTT button. When the control board receives this command,
the gate will open and by keeping this contact closed for all the time of the gate opening, the
Clock Function is automatically activated. In fact, once reached the open position, the gate
will remain opened and all of the control board functions are blocked. Only when K BUTT
contact is released, the control board functions are re-activated and the Automatic Closing
restarts (if enabled) doing the countdown to the gate closing.
PEDESTRIAN command (PED BUTT - COM)
This command is useful to open the gate partially, just enough, for example, to permit
a pedestrian crossing. In fact, the Pedestrian command (see Point E) is carried out only
by opening the gate just enough for a pedestrian to pass, as described into the Point E
procedure.
From the Pedestrian opening position the Automatic Closing can be enabled or disabled with
DIP3. From the Pedestrian opening position, the gate can be completely opened by the OPEN
or by the K BUTT button or by the RADIO button.
AUTOMATIC CLOSING (from the COMPLETE open position)
The Automatic Closing from the complete open position can be enabled turning ON the DIP3.
The maximum gap of time that can be programmed is 5 minutes (see Point D).
AUTOMATIC CLOSING (from the PEDESTRIAN open position)
The Automatic Closing from the pedestrian open position can be enabled turning ON the
DIP3. The maximum gap of time that can be programmed is 5 minutes (see Point E).
FUNCTIONING OF SAFETY ACCESSORIES
PHOTOCELL (PHOT - COM)
In case the switch DIP4 is in the OFF position, the photocells are active both in gate opening
and in gate closing. In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will stop and will restart opening when the obstacle is
removed
- while the gate is still, it will not move neither in opening nor in closing.
In case of the switch DIP4 is in the ON position, the photocells are active only in gate closing.
In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will continue open
- while the gate is still, it will open if a open command is request, it will remain still if a close
command is request.
The photocell input (PHOT - COM) is a NORMALLY CLOSED contact.
In case there are more couple of photocells, the contacts from all the photocell receivers
must be connected in series.
In case the photocells are not installed, this contact must be short circuited with a wire jump
(from PHOT to COM) to permit the gate to operate.
SAFETY STRIP (EDGE - COM)
If it intervenes during opening, it inverts the movement and closes for 2 seconds and then
stops.
If it intervenes during closing, it inverts the movement and opens for 2 seconds and then
stops.
If the safety strip remains engaged (NO contact), no automatic movement is allowed.
In case the safety strip is not installed, this contact must be short circuited with a wire jump
(from EDGE to COM) to permit the gate to operate.
PAY ATTENTION: it is highly recommended to check safety-strips operation at least every
6 months.
SAFETY STRIP ALARM
After the inversion given by the intervention of the safety edge, the gate stops in alarm mode
and this is signaled by the blinker on for 1 minute and by the buzzer on for 5 minutes.
During or after the minute of alarm, the normal gate operations can be restored by pressing
any push button.
TESTING THE SAFETY STRIP equipment
The DIP10 ON enables to test the safety strip equipment. The test is performed every time the
gate completes a full opening. The test is available only if the safety strip device is equipped
with a dedicated power supply input.
In fact, the safety strip equipment power supply input can be connected to the A+TEST and
A- outputs (DIP10 ON). Automatically, every time the gate completes a full opening, just
before closing, the control board switches OFF the A+TEST and A- power supply output for a
very short time. While the safety strip power supply is switched OFF, if everything is working
fine the safety strip contact (EDGE - COM) must open. In case the test fails, no other gate
manoeuvre will be allowed and the alarm state will be signalled by both the Blinker and the
Buzzer, if installed, which will remain on for 5 minutes.
NOT ALL THE SAFETY STRIPS CAN BE TESTED, THUS THE SWITCH DIP10 MUST BE LEFT
OFF.
STOP BUTTON
If the Automatic command is enabled (DIP 6 OFF), a Normally Closed contact could be
connected in series to the COM wire of the opened and the closed limit switches.
This contact works like a STOP button to interrupt any gate manouver.
FUNCTIONING IN DEAD MAN MODE WHEN THE SAFETY DEVICES ARE FAILING
If the safety edge fails or remains engaged for more than 5 seconds, or if photocell fails or
remain engaded for more than 60 seconds, the K BUTTON and PEDESTRIAN commands will
work only in dead man mode.
The signal that this mode has been activated is given by the blinking of the programming led.
With the blinking of the programming led, the opening and closing operation are allowed
only with the command button pressed and held. The radio commands and that of automatic
closing, will be excluded, since their use in this mode, is not allowed by the norms.
Once the failing safety device is repaired, in automatic after 1 second, all standard
31
G
B

Publicité

loading

Ce manuel est également adapté pour:

K2007Aa33694Aa33695Aa33753wAa33693Aa33696