Installation and operating instructions Wilo-Control EC-L
Commissioning
Menu no.
1.12*
Description
Base-load pump On level
Value range**
0.06 ... 12.5 m
Factory setting
0.40 m
Operating mode "drain": Value must be 0.03 m higher than
the "Base-load pump Off level" (menu 1.13).
Explanation
Operating mode "fill": Value must be 0.03 m lower than the
"Base-load pump Off level" (menu 1.13).
Menu no.
1.13*
Description
Base-load pump Off level
Value range**
0.06 ... 12.5 m
Factory setting
0.23 m
Operating mode "drain": Value must be 0.03 m lower than
the "Base-load pump On" level (menu 1.12).
Explanation
Operating mode "fill": Value mandatory 0.03 m higher than
the "Base-load pump On level" (menu 1.12).
Menu no.
1.14*
Description
Level peak-load pump 1 on
Value range**
0.06 ... 12.5 m
Factory setting
0.42 m
Operating mode "drain": The value must be 0.03 m higher
than the "Peak-load pump 1 On" level (menu 1.15). The
switch-on level must be greater than/equal to the switch-
on level of the base-load pump (menu 1.12).
Explanation
Operating mode "fill": The value must be 0.03 m lower than
the "Peak-load pump 1 Off" level (menu 1.15). The switch-
on level must be lower than/equal to the switch-on level
of the base-load pump (menu 1.12).
Menu no.
1.15*
Description
Peak-load pump 1 Off level
Value range**
0.06 ... 12.5 m
Factory setting
0.25 m
Operating mode "drain": Value mandatory 0.03 m lower
than the "Peak-load pump 1 On" level (menu 1.14). The
switch-off level must be greater than/equal to the switch-
on level of the base-load pump (menu 1.13).
Explanation
Operating mode "fill": Value must be 0.03 m higher than
the "Peak-load pump 1 On" level (menu 1.14). The switch-
off level must be lower than/equal to the switch-off level
of the base-load pump (menu 1.13).
Menu no.
1.16*
Description
Peak-load pump 2 On level
Value range**
0.06 ... 12.5 m
Factory setting
0.42 m
Operating mode "drain": The value must be 0.03 m higher
than the "Peak-load pump 2 Off" level (menu 1.17). The
switch-on level must be greater than/equal to the switch-
on level of the peak-load pump (menu 1.14).
Explanation
Operating mode "fill": The value must be 0.03 m lower than
the "Peak-load pump 2 Off" level (menu 1.17). The switch-
on level must be lower than/equal to the switch-on level
of the peak-load pump (menu 1.14).
en
85