Installation and operating instructions Wilo-Control EC-L
Commissioning
Menu no.
5.59
Description
Collective fault signal (SSM) function
Value range
fall, raise
Factory setting
raise
"fall": The relay is deactivated. Optionally, this function can
Explanation
be used for controlling the mains voltage supply.
"raise": The relay is activated.
Menu no.
5.62
Description
Dry-running protection delay
Value range
0 ... 180 s
Factory setting
0 s
Menu no.
5.64
Ex-mode operation On/Off (only available in the "drain"
Description
operating mode!)
Value range
on, off
Factory setting
off
If pumps and signal transmitters are connected in explosive
atmospheres, additional requirements must be adhered to.
Explanation
DANGER! Risk of explosion due to incorrect configuration
of the system! Observe the section on explosive atmo-
spheres in the appendix!
Menu no.
5.65
Description
Automatic resetting of error "Dry run"
Value range
on, off
Factory setting
on
Menu no.
5.66
Description
Integrated buzzer On/Off
Value range
on, off
Factory setting
off
NOTICE! Alarm in the event of interrupted power supply: To switch off the internal
buzzer if there is a built-in rechargeable battery, remove the battery!
Menu no.
5.67
Output (24 V DC, max. 4 VA) for an external signalling unit
Description
On/Off
Value range
off, error
Factory setting
off
en