84
Commissioning
Menu no.
5.68
Description
Mains connection rotating field monitoring On/Off
Value range
on, off
Factory setting
on
NOTICE! Switch off during alternating current connection!
Menu no.
5.69
Description
Motor current monitoring On/Off
Value range
on, off
Factory setting
on
NOTICE! Switch off during alternating current connection!
Menu no.
5.70
Description
Max. switching frequency per hour, per pump
Value range
0 ... 60
Factory setting
0
If the max. number of starts has been exceeded, the col-
Explanation
lective fault signal (SSM) is activated. Value "0" = function
deactivated.
Menu 1: Values for switching on and off
*NOTICE! The menu items 1.12 to 1.17 are only visible if, in menu 5.07, the value
"Level" or "Bell" have been set.
**NOTICE! The actual value range is dependent on the setting in menu 5.09.
Menu no.
1.09
Description
Base-load pump switch-off delay
Value range
0 ... 60 s
Factory setting
0 s
Menu no.
1.10
Description
Activation delay, peak-load pump
Value range
0 ... 30 s
Factory setting
3 s
Menu no.
1.11
Description
Switch-off delay peak-load pump
Value range
0 ... 30 s
Factory setting
1 s
WILO SE 2018-12