8.3
Connection of signal transmitters
and pumps within potentially ex-
plosive atmospheres
8.4

Activating the device

78
Commissioning
DANGER
Risk of explosion if the switchgear is installed in potentially explosive
areas!
The switchgear does not have its own explosion protection class and must always be
installed outside of potentially explosive areas! The connection must be made by a
qualified electrician.
DANGER
Risk of explosion due to incorrect connection!
If pumps and signal transmitters are connected in explosive atmospheres, there is a
risk of explosion due to incorrect connection. Observe the section on explosive at-
mospheres in the appendix!
NOTICE
Error message during operation at the alternating current connection
The switchgear has a rotating field monitor and motor current monitor. Both monit-
oring functions only work trouble-free at the three-phase current connection and
are activated at the factory. If the switchgear is used at an alternating current con-
nection, the following error messages are shown in the display:
• Rotating field monitoring: Error code "E006"
⇒ Switching off rotating field monitoring: Select Menu 5.68, value "off"!
• Motor current monitoring: Error code "E080.x"
⇒ Switching off the motor current monitoring: Select Menu 5.69, value "off"!
▶ Monitoring functions deactivated. The switchgear now works trouble-free at the
alternating current connection.
NOTICE
Observe the error code in the display
If the red fault LED lights up or flashes, observe the error code on the display! If the
error has been confirmed, the previous error is stored in menu 6.01.
NOTICE
Operating mode after power failure
Following a power failure, the switchgear will automatically start up in the last oper-
ating mode set.
Switchgear is closed.
Installation has been performed correctly.
All signal transmitters and consumers are connected and installed in the operating
space.
If float switches are used, set the switching points correctly.
Motor protection is preset according to the pump data.
1. Turn the main switch to the "ON" position.
2. Switchgear starts.
All LEDs light up for 2 s.
– The display illuminates and the start screen appears.
- The standby symbol appears in the display.