Commissioning
Menu no.
5.43
Description
"Pump kick running time"
Value range
0 ... 60 s
Factory setting
5 s
Menu no.
5.44
Description
Activation delay after power failure
Value range
0 ... 180 s
Factory setting
3 s
Menu no.
5.50
Description
Dry-running level (drain)/ min. water level (fill)
Value range
0 ... 12.5 m
Factory setting
0.15 m
If the level is monitored with a separate float switch, deac-
Explanation
tivate the level sensor: Enter the value "0.00 m".
Menu no.
5.51
Description
High water level
Value range
0 ... 12.5 m
Factory setting
0.46 m
Menu no.
5.57
Description
Max. running time per pump
Value range
0 ... 60 min
Factory setting
0 min
Maximum permissible running time of a pump. Once the
time has been exceeded, the system switches to the next
pump. After three change cycles, the collective fault signal
Explanation
(SSM) is activated.
The setting "0 min" switches the running time monitoring
off.
Menu no.
5.58
Description
Collective run signal (SBM) function
Value range
on, run
Factory setting
run
"on": Switchgear ready for operation
Explanation
"Run": At least one pump is running.