Installation and operating instructions Wilo-Control EC-L
Commissioning
Menu no.
5.09
Description
Sensor measuring range
Value range
0.25 ... 12.5 m
Factory setting
1.0 m
Menu no.
5.39
Description
Alarm signal with active "Extern OFF" input
Value range
off, on
Factory setting
off
The pumps can be switched off using a separate signal
transmitter via the "Extern OFF" input. This function over-
rides all other switching points and all pumps are switched
off.
In the "fill" operating mode it can be determined how the
alarm signal occurs in the event of an active input:
Explanation
– "off": The "Extern OFF" symbol appears on the LCD dis-
play
– "on": The "Extern OFF" symbol and the error code "E068"
appears on the LCD display.
In the "drain" operating mode, the factory setting cannot
be changed!
Menu no.
5.40
Description
Function "pump kick" On/Off
Value range
off, on
Factory setting
off
To prevent longer standstill times for the connected
pumps, a periodical test run can be performed (pump kick
function). If the pump kick function is activated, the fol-
Explanation
lowing menu items can be set:
– Menu 5.41: Pump kick permitted in Extern OFF
– Menu 5.42: Pump kick interval
– Menu 5.43: Pump kick-running time
Menu no.
5.41
Description
"Pump kick" permitted in Extern OFF
Value range
off, on
Factory setting
on
Menu no.
5.42
Description
"Pump kick interval"
Value range
1 ... 336 h
Factory setting
24 h
en
81