Electrical Installation; Emc−Compliant Wiring - Lenze APPLICATION−I/O PT E82ZAFAC010 Instructions De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4

Electrical installation

EMC−compliant wiring
4
Electrical installation
EMC−compliant wiring
Please observe the following for wiring according to EMC guidelines:
)
Note!
Separate control cables from motor cables.
ƒ
Lead the shields as far as possible to the terminals (unshielded core length
ƒ
< 40 mm).
Connect control and data cable shields as follows:
ƒ
– Analog signal cable shields must be connected with one end at the
inverter.
– Digital signal cable shields must be connected with both ends.
More information about wiring according to EMC guidelines can be
ƒ
obtained from the corresponding documentation for the standard device.
30
l
EDK82ZAFAC−010 DE/EN/FR 6.0

Publicité

Table des Matières
loading

Table des Matières