SELECTION OF CONTROL BOARD FUNCTIONS AND MODES (SW2)

Using SW2, choose the required options (see "SW2 functions" on page 32).
7

POTENTIOMETER ADJUSTMENT

P1 P2 P3
ST1
FT1
8

START UP

Final checks
Following installation and programming, start up the
operators and check the devices installed:
1 Check the correct working of the key devices (push
button, key switch and transmitter).
See "Functioning modes" on page 25.
2 Check the correct operation of the safety devices
(photocells or mechanical strips).
See "A- Detection by safety device (photocell or
mechanical strip)" on page 26.
3 If everything is correct, close the control board
cover.
FCA2 COM FCC2
SCA
P4 P5 P6
P15 P14 P16
P7 P8
P11 P12
P22
24Va
ST2
FT2
FCA1
FCC1
STOP
LOCK
P167M
PROGRAMMING AND STARTUP
Regulation of lapse time between the leaves (T.D.)
With the potentiometer set to the minimum there is no
delay time in opening or closing, i.e. the two leaves
begin to open at the same time and end up closing at
the same time. With the potentiometer set at more
than the minimum, the delay time on the opening will
be approximately three seconds, and up to 20 seconds
maximum on closing.
When using a single operator, set T.D. to the
minimum.
Regulation of garage light time (T.LG)
If the garage lighting circuit has been connected to the
control board, regulate the time which the lamps shall
remain on using T.LG.
Minimum value: 3 seconds; maximum value: 90
seconds.
Setting standby time (T.E.)
If automatic operation mode has been programmed
(DIP4=ON), adjust T.E. to adjust standby time with the
gate open (before automatic closing begins).
Minimum value: 3 seconds; maximum value: 60
seconds.
Torque adjustment (P.M.)
Correct
torque
adjustment
importance to prevent injury and damage.
Increased torque produces a more violent
impact.
• Hydraulic operators: set P.M. at the maximum value.
• Electromechanical
operators:
detection sensitivity to be adjusted (DIP9). Set P.M
at the minimum value possible, compatible with the
proper operation of the gate.
If the system does not work correctly, find out
why and put it right (see section "Failure
diagnosis" on page 38).

User instruction

1 Instruct the user with regards to the use and
maintenance of the installation and provide him/her
with the user guide.
2 Signpost
the
gate,
automatically and indicating how to operate it
manually.
Where
appropriate,
operation is using the remote control.
is
of
vital
allows
obstacle
showing
that
it
opens
indicate
that
Control board VIVO-M201(M)
37