SELECTING CONTROL BOARD FUNCTIONS AND MODES (SW2)

Choose the required options using SW2 (see "SW2 functions" on page 48).
5

SWITCH AND POTENTIOMETER SETTINGS

IZ4 IZ1
J1
IZAR4
L6
IZAR1
STOP
T.E.
Open door stand-by time adjustment
(only
works
DIP1=ON)
J1
Operator model jumper
(IZAR 1 - IZAR 4)
PM.A Torque adjustment (maximum thrust) in
opening
PM.C Torque adjustment (maximum thrust) in
closing
J1 must be placed in the position
corresponding to the operator installed
(IZAR1 or IZAR4). Failure to do so may
lead to accidents.
P29OA
in
automatic
mode,
PROGRAMMING AND STARTUP
Open door standby time (T.E.)
If automatic operation mode has been programmed
(DIP1=ON), adjust T.E. to set stand-by time with the
door open (before automatic closing begins). Turn
clockwise to increase stand-by time.
Approximate maximum value: 45 seconds.
Selecting operator model (J1)
Select the operator model (IZAR 4 or IZAR 1) using J1.
O
Using an incorrect J1 position may cause the
motor to deteriorate.
Torque adjustment (PM.A and PM.C)
Correct torque and speed adjustment is of vital
importance for the door to stop automatically
when coming across a possible obstacle
without producing any injury or damage.
Increased torque produces a more violent
impact.
• Adjust the torque limitation potentiometers (PM.A
for opening and PM.C for closing) at the minimum
value possible compatible with proper operation of
the door.
The maximum torque decreases in anti-clockwise
direction (the force of collision against an
obstacle decreases).
The maximum torque increases in clockwise
direction (the force of collision against an
obstacle increases).
VIVO-D103 / ADB30 Control board
51