Commissioning Assistant; Menu Overview Commissioning Assistant (Wizard) - Helios AIR1 XH 1000-8500 Notice De Montage Et D'entretien

Table des Matières

Publicité

Installation and Operating Instructions
EN
Central ventilation units AIR1 XH

Commissioning Assistant

2 .3 .1 Menu overview Commissioning assistant (wizard)

Commissioning Assistant (for control unit AIR1 BE-ECO)
Ceiling units plate
Choose con guration
AIR1 XC 700
Floor units plate
Choose con guration
None
Floor units rotary
Choose con guration
None
Choose Language
English
External 0-10V
control
No
Control function-
Mode
->
Supply air control
SAF CAV setp
Ventilation-
Reduced: 150 m3/h
Mode
Normal: 400 m3/h
Constant air ow
Boost: 600 m3/h
EAF CAV setp
Electrical
preheater
Reduced: 150 m3/h
Normal: 400 m3/h
No
Boost: 600 m3/h
Supply lter type
ePM1 55% (F7)
Extract lter type
ePM10 50% (M5)
After heater type
None
Cooler type
None
Free cooling
(Night cooling)
Yes ->
Sensor-Type
Ventilation on
Rel. Humidity*
demand
CO2/mixed gas (VOC)*
No
*
Menus are only
Accept all settings
visible after
and activate the
the corresponding
application
sensor type has
No
been assigned to an
analog input.
Main-
menu
Start
after rst
power
supply
Supply air temp***
Setp: 22.0 °C
Neutral Zone
0.0 °C
outd temp activation
22 °C
Outd temp night
High: 18.0°C
Low: 10.0°C
Room temp min 18.0°C
Hour for start/stop
free cooling
Start: 0
Stop: 7
Time to block heat
output after
free cooling
60 Min
Outdoor sensor
placed in intake
channel
No
Minimal: 80
Boost: 100 %
Di :
16
Stop-time: 2
Minimal: 800 ppm
Boost: 1000 ppm
Di :
160 ppm
Stop-time: 2
35
***
Di erent temperature
Sub-menus depending on selected
Temperature control mode
Sensor-Type
AI2: Rel. Humidity**
%
Sensor-Type
AI3: mixed gas (VOC)
Std
Sensor-Type
AI4: CO2
Std
**
Analog input AI2 not available for air
quality sensors, if temperature-control
mode with room temperature
sensor selected