NOTE
Compact wall-mounted units KWL EC 500 W ET R/L
2 .9

Functional layout

When using a heater battery, the duct system must be fitted with temperature-resistant
Bei Verwendung eines Heizregisters, muss das Rohrsystem 0,5m vor und nach dem Heizregister
or non-combustible ducting 0.5 m before and after the heater battery (e.g. spiral duct)
mit temperaturbeständigem bzw. nicht brennbarem Rohr versehen werden (z.B. Wickelfalzrohr)
Extract air
Abluft
Supply air
Zuluft
T6
1
Pos.
Benennung
Description
T1
Außenluftfühler
Outside air sensor
T2
Zuluftfühler
Supply air sensor
Extract air sensor
T3
Abluftfühler
Exhaust air sensor
T4
Fortluftfühler
T6
Kanalfühler Type: KWL-LTK (Zubehör)
Duct sensor type KWL-LTK (accessories)
T7
Frostschutzfühler Type: KWL-LTK (Zubehör) für WW-Register Rücklauf
Frost protection sensor type KWL-LTK (accessories) for HW register return
F-AB
Feuchtefühler intern
Humidity sensor internal
CO2-Fühler : KWL-CO2 (Zubehör)
CO2 sensor KWL-CO2 (accessories)
External
Externe
Feuchte/Temperaturfühler: KWL-FTF (Zubehör)
Humiditytemp. sensor KWL-FTF (accessories)
Fühler
sensors
VOC sensor KWL-VOC (accessories)
VOC-Fühler : KWL-VOC (Zubehör)
1
Temperaturbeständiges bzw. nicht brennbares Rohr (z.B. Wickelfalzrohr)
Temperature-resistant or non-combustible ducting (e.g. spiral duct)
Iso-Pipe ducting Ø125
2
Iso-Pipe Rohr
Verbinder mit Dichtung für Geräteanschluss ans Rohrsystem: RVBD 160 K
Connector with seal for unit connection to duct system.
3
4
Elektrische Vorheizung intern: KWL EVH 500
Electrical pre-heater internal KWL EVH 500
Electrical auxiliary heater type EHR-R 2,4/16 (accessories)
5
Note: KWL-LTK included in delivery for EM module
Alternative: Hot water auxiliary heater type WHR 160 (accessories) with
hydraulic unit

2 .10 Initial commissioning and adjustment

Useful hint for adjustment!
The adjust ment by means of pressure measurement is explained in the Helios practical workshops, and this is the
easiest way to adjust a KWL EC 500 W ET R/L. In this respect, a pressure measuring connector must be mounted to
each connecting socket/ventilation pipe (approx. 20 cm past the unit connection), and the pressure hoses must be
readily accessible.
To balance the whole system, supply and extract openings should be provided with adjustable elements or valves
(accessories). During extraction of polluted extract air, a filter (accessories) is to be connected. The installation of kitchen
hoods to the system (cause: dirt, fire danger, hygiene) is not permitted. To ensure air circulation within the room suffi-
cient overflow openings (door gap, door grilles) are to be planned.
Any fire regulations must be observed!
Detailed information on the adjustment of KWL wall-mounted units can be found in the Installation and
Operating Instructions "KWL easyControls Initial Commissioning"; No . 82 237!
T3
(T7)
5
Return
Rücklauf
WW-Register
1
HW register
1
T2
T1
F-AB
Fig. KWL EC 500 W ET right
Abb. KWL EC 500 W ET Rechts
Abb. KWL EC 500 W Rechts
160
Elektrische Nachheizung Type: EHR-R 2,4/160 (Zubehör)
Hinweis: Beim EM-Modul ist im Lieferumfang ein KWL-LTK enthalten
Alternativ:
Warmwasser Nachheizung Type: WHR 160 (Zubehör) mit Hydraulikeinheit
9
2
3
T4
External sensor
Externe Fühler
(interior installation)
(Raumseitige Installation)
CO2 sensor
CO2-Fühler
Humiditytemp. sensor