Installation and Operating Instructions
m
NOTE
m
ATTENTION
Compact wall-mounted units KWL EC 170 W / W ET
2 .8

Functional layout

When using a heater battery, the duct system must be fitted with temperature-resistant or non-
combustible ducting 0.5 m before and after the heater battery (e.g. spiral duct)
Supply air
1
External sensor
(room-side installation)
• CO2 sensor
• Humidity/temperature sensor
• VOC sensor
Pos.
Name
Humidity/temperature sensor: KWL-FTF (Accessories)
External
sensor
VOC sensor: KWL-VOC (Accessories)
1
Temperature-resistant or non-combustible ducting (e.g. spiral duct)
2
Iso-Pipe pipe
3
Connector with seal for unit connection to duct system: RVBD 125 K
4
Note: A KWL-LTK is included in scope of delivery for the Beim EM module
Hot water auxiliary heater type: WHR 125 (Accessories) with hydraulic unit
2 .9

Initial commissioning and adjustment

Useful hint for adjustment!
The adjustment by means of pressure measurement is explained in the Helios practical workshops, and this is the
easiest way to adjust a KWL EC 170 W / W ET. In this respect, a pressure measuring connector must be mounted to
each connecting socket/ventilation pipe (approx. 20 cm past the unit connection), and the pressure hoses must be
readily accessible.
To balance the whole system, supply and extract openings should be provided with adjustable elements or valves
(accessories). During extraction of polluted extract air, a filter (accessories) is to be connected. The installation of kit-
chen hoods to the system (cause: dirt, fire danger, hygiene) is not permitted. To ensure air circulation within the room
sufficient overflow openings (door gap, door grilles) are to be planned.
All fire protection regulations must be observed!
Detailed information on the adjustment of KWL wall-mounted units can be found in the Installation and
Operating Instructions "KWL easyControls Initial Commissioning"; No . 82 237!
Extract air
2
4
1
3
125
Electrical auxiliary heater type: EHR-R 1,2/125 (accessories)
Alternative:
9
Fig .16
Outside air
2
Exhaust air
Fig. KWL EC 170 W