Installation and operating instructions
GB
CHAPTER 3

FUNCTIONAL DESCRIPTION

NOTE
ATTENTION
Passive house compact units KWL EC 270/370 W R/L
3.0

Functional layout

Pos.
Name
T1
Outside air sensor
T2
Supply air sensor
T3
Extracted air sensor
T4
Outgoing air sensor
T5
Duct sensor Type KWL-LTK (accessories)
T6
Duct sensor Type KWL-LTK (accessories)
T7
Frost-protection sensor Type KWL-LTK (accessories) for WW-register return
T11-T18
Humidity/temperature sensor: KWL-FTF
1
Temp-resistant or non-flammable duct (e.g. spiral duct)
2
Temp-resistant or non-flammable insulation
3
Iso-Pipe duct Ø 160
Pre-heater type: EHR-R 1.2/160
4
5
Air filter box type: LFBR 160 G4
Electric auxiliary heater Type EHR-R 2.4/160
6
Hot water auxiliary heater Type: WHR 160
and hydraulic unit
Alternative
3.1

Initial start-up and adjustment

Useful hint for adjustment!
The adjustment by means of pressure measurement is explained in the Helios practical workshops, and
this is the easiest way to adjust a KWL EC 270/370 W R/L. In this respect, a pressure measuring
connector must be mounted to each connecting socket/ventilation pipe (approx. 20 cm past the unit
connection), and the pressure hoses must be readily accessible. To balance the whole system, supply
and extract openings should be provided with adjustable elements or valves (accessories). During
extraction of polluted extract air, a filter (accessories) is to be connected. The installation of kitchen
hoods to the system (cause: dirt, fire danger, hygiene) is not permitted. To ensure air circulation within
the room sufficient overflow openings (door gap, door grilles) are to be planned.
All fire regulations must be observed!
Detailed information on the adjustment of KWL wall-mounted units can be found in the
TIP!
Installation and Operating Instructions "KWL easyControls Initial start-up"; No. 82 237!
Fig. KWL EC 270/370 W Right
+ KWL EM
+ KWL LTK
+ KWL EM
+ KWL LTK
+ WHSH 1100 24V (0-10V)
+ KWL EM
+ 2x KWL LTK (T6+T7)
8
Item No.
-----
-----
-----
-----
09644
09644
09644
04273
-----
-----
09434
04269
09644
08578
09435
04269
09644
09481
08819
04269
09644