Functional Layout; Initial Start-Up And Adjustment; Rj Connections With Easycontrols - Helios KWL EC 220 D R Instructions D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and operating instructions
GB
NOTE
ATTENTION
Compact ceiling-mounted units KWL EC 220/340 D
1.14

Functional layout

Pos.
Name
T1
Outside air sensor
T2
Supply air sensor
T3
Extracted air sensor
T4
Outgoing air sensor
T6
Duct sensor Type KWL-LTK (accessories)
T7
Frost-protection sensor Type KWL-LTK (accessories) for WW-register return
T11-T18
Humidity/temperature sensor: KWL-FTF (accessories)
Pipe connector: RVBD 125
1
Iso-Pipe duct Ø 125
2
Connection spigot: IP-MU 125
3
Electric pre-heater internal: KWL EVH 220 D
4
Electric auxiliary heater Type EHR-R 1.2/125 + KWL EM + KWL LTK
5
Hot water auxiliary heater Type: WHR 125
and hydraulic unit
Alternative
1.15

Initial start-up and adjustment

Useful tip for adjustment!
In the Helios practise workshops, the adjustment is confirmed by means of pressure measurement, which
is the easiest way of adjusting a KWL EC ... D R/L. In this respect, a pressure measuring connector must
be mounted to each connecting piece/ ventilation pipe (approx. 20 cm after the unit connection); the
pressure hoses must be easily accessible.
In order to adjust the system, supply and extracted air openings should be provided with adjustable
elements or valves (accessories). When extracting polluted extracted air, a filter (accessories) must be
located upstream. Extraction hoods must not be connected to the system (reasons: Dirt, fire hazard,
hygiene). In order to ensure air flow within the room, sufficient overflow openings (door gaps, door
ventilation grilles) should be provided.
All existing fire protection provisions must be observed!
TIP!
Detailed information on the adjustment of KWL ceiling units can be found in the Installation and
Operating Instructions „KWL easyControls Initial start-up"; No. 82 237!
1.16

RJ connections with easyControls

TIP!
Take note of the information in the "easyControls" user manual (No. 82 200).
Fig. KWL EC 200/300 W Right
RVBD 160
Ø 160
IP-MU 125
KWL EVH 340 D
EHR-R 2.4/160 + KWL EM + KWL LTK
WHR 160
+ WHSH 1100 24V (0-10V)
+ KWL EM
+ 2x KWL LTK (T6+T7)
4
Item No.
-----
-----
-----
-----
09644
09644
04273
09640
09641
09406
09447
09394
09453
09636
04241
09433
09435
04269
09644
09480
09481
08819
04269
09644