Installation and Operating Instructions
m
NOTE
m
ATTENTION
Compact wall-mounted units KWL EC 200/300 W ET R/L
2 .8

Functional layout

When using a heater battery, the duct system must be fitted with temperature-resistant or non-combustible
ducting 0.5 m before and after the heater battery (e.g. spiral duct)
Supply air
1
T6
Extract air
Pos.
Description
T1
Outside air sensor
T2
Supply air sensor
T3
Extract air sensor
T4
Exhaust air sensor
T6
Duct sensor type: KWL-LTK (accessories)
T7
Frost protection sensor type: KWL-LTK (accessories) for HW register return
F-AB
Humidity sensor internal
CO2 sensor : KWL-CO2 (accessories)
External
Humidity/temp. sensor : KWL-FTF (accessories)
sensors
VOC sensor : KWL-VOC (accessories)
1
Temperature-resistant or non-combustible ducting (e.g. spiral duct)
2
Iso-Pipe ducting
3
Connector with seal for unit connection to duct system: RVBD 125 K
4
Electrical pre-heater internal: KWL EVH 200/300W
5
2 .9

Initial commissioning and adjustment

Useful hint for adjustment!
The adjust ment by means of pressure measurement is explained in the Helios practical workshops, and this is the
easiest way to adjust a KWL EC 200/300 W ET R/L. In this respect, a pressure measuring connector must be mounted
to each connecting socket/ventilation pipe (approx. 20 cm past the unit connection), and the pressure hoses must be
readily accessible.
To balance the whole system, supply and extract openings should be provided with adjustable elements or valves
(accessories). During extraction of polluted extract air, a filter (accessories) is to be connected. The installation of kitchen
hoods to the system (cause: dirt, fire danger, hygiene) is not permitted. To ensure air circulation within the room suffi-
cient overflow openings (door gap, door grilles) are to be planned.
Any fire regulations must be observed!
Detailed information on the adjustment of KWL wall-mounted units can be found in the Installation and
Operating Instructions "KWL easyControls Initial Commissioning"; No . 82 237!
(T7)
5
Return
HW register
1
T2
1
T3
T4
F-AB
Fig. KWL EC 200/300 W right
125
Electrical auxiliary heater type: EHR-R 1,2/125 (accessories)
Note: KWL-LTK included in delivery for EM module
Alternative:
Hot water auxiliary heater type: WHR 125 (accessories) with hydraulic unit
9
2
2
T1
3
Exhaust air
External sensor
(interior installation)
• CO2 sensor
• Humidity/temp. sensor
• VOC sensor
EN