Unit Selection; External Control 0; Temperature Control Mode - Helios AIR1 XH 1000-8500 Notice De Montage Et D'entretien

Table des Matières

Publicité

Installation and Operating Instructions
EN
Central ventilation units AIR1 XH

2 .3 .4 Unit selection

Selection of the applicable ventilation units in 3 groups:
• Ceiling unit with cross counter-flow heat exchanger (X-WT)
• Standing unit with cross counter-flow heat exchanger (X-WT)
• Standing unit with rotary heat exchanger (Rot-WT)
Only one ventilation unit can be selected. The word "None" appears automatically in the other two windows. The last
setting is valid.
Ceiling unit X-WT
Choose configuration
None
2 .3 .5 External control 0-10 V
Selection of "External 0-10 V" control. In case of external fan control, this mode must be selected if an external cont-
roller regulates the air flow.
Select Yes/No:
External 0-10V
control
No

2 .3 .6 Temperature control mode

The temperature control influences the existing heating and cooling registers:
• Electrical heating
• Warm water heating
• DX cooling
• Cold water cooling
The temperature control mode can only be set by the commissioning assistant (wizard). The following temperature
control modes are available:
a . Constant Supply Air Control
b . Outdoor Compensated Supply Air Control
c . Cascade Room Temperature Control
d . Cascade Extract Air Temperature Control
e . Outdoor Temperature Dependent Supply or Room Temperature Control
f . Outdoor Temperature Dependent Supply or Extract Temperature Control
g . Outdoor Temperature Dependent Room Temperature Control
h . Outdoor Temperature Dependent Extract Air Control
a . Constant Supply Air Control
The heating and cooling outputs can only be adjusted to the supply air sensor in Constant Supply Air Control mode. A
neutral zone can be defined for the setpoint.
Example: If the setpoint is 18 °C and the neutral zone (NZ) is 2°C: Setpoint heating = 17°C and setpoint cooling = 19°C.
If the supply air temperature is in the neutral zone "heating" and "cooling" are blocked. If the supply air temperature falls
below the setpoint -NZ/2, the "heating" mode will be active until the setpoint is reached. If the supply air temperature
rises above the setpoint +NZ/2, the "cooling" mode will be active until the setpoint is reached.
The setpoint is displayed in the "temperature" menu (log in as User or Admin):
Temp. control mode
Supply air control
Supply air temp.
Setp: XX.X °C
Neutral zone
X.X °C
b . Outdoor Compensated Supply Air Control
The supply air temperature setpoint can be set to improve the regulation of room heat losses due to the outdoor tem-
perature. This ensures that the cooling of room walls is compensated for during the cold season.
The supply air temperature setpoint is compensated for depending on the outdoor temperature using a control curve
with 8 points.
AIR1 RH series
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
37
AIR1 XC series
AIR1 XH series
OK
OK
OK
OK
OK
OK
OK
OK

Publicité

Table des Matières
loading

Table des Matières