Sensor Settings; Control Function - Helios AIR1 XH 1000-8500 Notice De Montage Et D'entretien

Table des Matières

Publicité

Installation and Operating Instructions
The submenus of configuration (Part 2 of 4)
Inputs / Outputs
AI
AI exp3
AI exp4
DI
UI
UI exp3
UI exp4
AO
DO

Control function

Control function
Mode:
Supply air control
All necessary Configurations are carried out in the commissioning assistant!
Central ventilation units AIR1 XH
AI1:
AI1...
Sign: Not used
AI4
Raw value: NaN
Comepnsation: 0.0
Pressure A exp3
Sign: SAF pressure
Raw value: 0.0
Compensation: 0.0 Pa
Pressure B exp3
Sign: Filtguard1
Raw value: 0.0
Compensation: 0.0 Pa
Pressure A exp4
Sign: EAF pressure
Raw value: 0.0
Compensation: 0.0 Pa
Pressure B exp4
Sign: Filtguard2
Raw value: 0.0
Compensation: 0.0 Pa
DI1:
DI1...
NO/NG: NO Signal:
DI8
Ext alarm1
Status: Off
UAI1:
UI1:
Sign: Not used
Choose AI or DI sign
Raw value: NaN
AI sign: Not used
Compensation: 0.0
DI sign: Not used
UI1...
UI4
UDI1:
NO/NG: NO Signal:
Not used
Status: Off
UAI1 Exp3:
UI1 Exp3:
Sign: Supply temp
Choose AI or DI sign
Raw value: 0.0
AI sign: Supplytemp
UI1
Compensation: 0.0
DI sign: Not used
Erweit.3
&
UI2
UAI Erweit.3:
Erweit.3
NO/NG: NO Signal:
Not used
Status: Off
UAI1 Exp4:
UI1 Exp4:
Sign: Exhausttemp
Choose AI or DI sign
Raw value: 0.0
AI sign: Exhausttemp
UI1
Compensation: 0.0
DI sign: Not used
Erweit.4
&
UI2
UDI Exp4:
Erweit.4
NO/NG: NO Signal:
Not used
Status: Off
AO1:
AO1...
Sign: Not used
AO5
Auto
Value: 0.0 V
DO1:
DO1...
Sign: Not used
DO7
Auto
Status: Off
Fan control
Outdoor temp for
Fan control
control mode change
Flow control
13.0 °C
Crosswise interlock
between SAF and EAF
No

Sensor settings

SAF pressure at
0.0V: 0.0
Pa
10.0V: 500.0 Pa
Filter factor: 0.2
EAF pressure at
0.0V: 0.0
Pa
10.0V: 500.0 Pa
Filter factor: 0.2
CO2 at
0.0V: 0.0
ppm
10.0V: 2000.0 ppm
Filter factor: 0.2
Room humidity at
0V: 0.0
% RF
10V: 100.0 % RF
Filter factor: 0.2
Filter guard1 at
0V: 0.0
Pa
10V: 500.0 Pa
Filter factor: 0.2
Filter guard2 at
0V: 0.0
Pa
10V: 500.0 Pa
Filter factor: 0.2
Filter factor
temperature: 0.2
Outd temp
Sensor type: PT1000
SAF flow control
factors
K-constant: 252
X-constant: 0.50
EAF flow control
factors
K-constant: 252
X-constant: 0.50
62
EN