Installation and Operating Instructions
The submenus of configuration (Part 2 of 4)
Inputs / Outputs
AI
AI1:
AI exp3
Sign: Not used
AI exp4
Raw value: NaN
DI
Comepnsation: 0.0
Pressure A exp3
UI
UI exp3
Sign: SAF pressure
Raw value: 0.0
UI exp4
AO
Compensation: 0.0 Pa
Pressure B exp3
DO
Sign: Filtguard1
Raw value: 0.0
Compensation: 0.0 Pa
Pressure A exp4
Sign: EAF pressure
Raw value: 0.0
Compensation: 0.0 Pa
Pressure B exp4
Sign: Filtguard2
Raw value: 0.0
Compensation: 0.0 Pa
DI1:
NO/NG: NO Signal:
Ext alarm1
Status: Off
UI1:
Choose AI or DI sign
AI sign: Not used
DI sign: Not used
UI1 Exp3:
Choose AI or DI sign
AI sign: Supplytemp
DI sign: Not used
UI1 Exp4:
Choose AI or DI sign
AI sign: Exhausttemp
DI sign: Not used
AO1:
Sign: Not used
Auto
Value: 0.0 V
DO1:
Sign: Not used
Auto
Status: Off

Control function

Control function
Outdoor temp for
Mode:
control mode change
Supply air control
13.0 °C
Central ventilation units AIR1 RH
AI1...
AI4
DI1...
DI8
UAI1:
Sign: Not used
Raw value: NaN
Compensation: 0.0
UI1...
UI4
UDI1:
NO/NG: NO Signal:
Not used
Status: Off
UAI1 Exp3:
Sign: Supply temp
Raw value: 0.0
UI1
Compensation: 0.0
Erweit.3
&
UI2
UAI Erweit.3:
Erweit.3
NO/NG: NO Signal:
Not used
Status: Off
UAI1 Exp4:
Sign: Exhausttemp
Raw value: 0.0
UI1
Compensation: 0.0
Erweit.4
&
UI2
UDI Exp4:
Erweit.4
NO/NG: NO Signal:
Not used
Status: Off
AO1...
AO5
DO1...
DO7

Fan control

Fan control
Flow control
Crosswise interlock
between SAF and EAF
No
66

Sensor settings

SAF pressure at
0.0V: 0.0
Pa
10.0V: 500.0 Pa
Filter factor: 0.2
EAF pressure at
0.0V: 0.0
Pa
10.0V: 500.0 Pa
Filter factor: 0.2
CO2 at
0.0V: 0.0
ppm
10.0V: 2000.0 ppm
Filter factor: 0.2
Room humidity at
0V: 0.0
% RF
10V: 100.0 % RF
Filter factor: 0.2
Filter guard1 at
0V: 0.0
Pa
10V: 500.0 Pa
Filter factor: 0.2
Filter guard2 at
0V: 0.0
Pa
10V: 500.0 Pa
Filter factor: 0.2
Filter factor
temperature: 0.2
Outd temp
Sensor type: PT1000
SAF flow control
factors
K-constant: 252
X-constant: 0.50
EAF flow control
factors
K-constant: 252
X-constant: 0.50
EN