Installation and Operating Instructions
Central ventilation units AIR1 RH
1. The gasket must be fitted between the adjoining modules before assembly of the module (see Fig. 15).
2. Prior to the assembly of the modules in the final position, they must be positioned as close together as possible.
Only the respective base frame may be used to pull the modules together.
3. Connect the modules electrically via the pre-wired connector.
4. Join the modules together using the connector (see Fig. 17) and the screws in the base frame.
2�2�6 Flange connection / adapters
The dimensions for the unit flange connections can be found in the following table.
X
R
T
W
Fig� 16
Fig� 17
Unit type
R
S
AIR1 RH 1500
378
338
AIR1 RH 2000
498
338
AIR1 RH 3000
608
438
AIR1 RH 5000
883
438
AIR1 RH 6000
883
438
AIR1 RH 8000
1083
438
AIR1 RH 9500
1228
438
AIR1 RH 12000
1503
538
AIR1 RH 15000
1628
738
n: Number of drill holes
Hole/screw dimensions: M8X16
12
Dimensions (mm)
T
U
V
W
350
310
470
310
580
410
855
410
498
855
410
498
1055
410
498
361,1
1200
410
498
409,4
1475
510
598
501,1
1600
710
798
814,2
EN
Fig� 15
Fig� 18
X
n
4
4
4
6
6
8
8
1563
10
1688
10