Helios AIR1 RH 1500 Notice De Montage Et D'utilisation page 124

Table des Matières

Publicité

Installation and Operating Instructions
EN
+
NOTE
Central ventilation units AIR1 RH
Example:
Outdoor temp� [°C]
-20
-15
-10
-5
0
5
10
15
Temp. control mode
Outdoor comp supply
Outdoor comp setp.
-20.0 °C = 25.0 °C
-15.0 °C = 24.0 °C
-10.0 °C = 23.0 °C
Outdoor comp setp.
-5.0 °C = 23.0 °C
-0.0 °C = 22.0 °C
-5.0 °C = 22.0 °C
Outdoor comp setp.
10.0 °C = 18.0 °C
15.0 °C = 18.0 °C
c� Cascade Room Temperature Control
Only possible with the humidity-temp. sensor KWL-FTF 0-10V accessory.
Connect the analogue output A2 (temp. signal) of the KWL-FTF 0-10V to the analogue input AI2 of the ventilation unit
(see wiring diagram).
The cascade control of the room and supply air temperature is used to maintain a constant, adjustable room tempe-
rature. The supply air temperature setpoint is set by the room temperature controller according to the deviation of the
ambient temperature from the room temperature setpoint.
The room temperature setpoint is displayed in the "temperature" menu (log in as User or Admin):
Temp. control mode
Cascade room ctrl
Room temp.
Setp: XX.X °C
If cascade control
Max/min supply setp.
Max: XX.X °C
Min: XX.X °C
d� Cascade Extract Air Temperature Control
The cascade control of the extract air and supply air temperature is used to maintain a constant, adjustable room tem-
perature. The extract air temperature controller output signal influences the supply air temperature controller setpoint.
The setpoint is displayed in the "temperature" menu (log in as User or Admin):
Temp. control mode
Cascade extract ctrl
Supply air temp� [°C]
25
24
23
23
22
20
18
18
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
41
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK

Publicité

Table des Matières
loading

Table des Matières