Installation and Operating Instructions
Central ventilation units AIR1 RH
• Call up holiday calendar
• Set holiday periods
Holiday (mm:dd)
1: XX-XX – XX-XX
2: XX-XX – XX-XX
3: XX-XX – XX-XX
4�1�3 Sensor-controlled operation (VOD - Ventilation on demand)
The sensor-controlled operation function (Ventilation on demand = VOD) must first be set in the commissioning
assistant.
The sensor-controlled operation only works in "Constant volume flow mode" or "Constant speed mode". The sen-
sor-controlled operation function can only be activated using the VOD timer.
The sensor-controlled operation is only used to achieve improved room air quality. In this respect, the use of air quality
sensors (KWL-CO2 0-10V, KWL-FTF 0-10V, KWL-VOC 0-10V) is required. This mode can also be used for
multiple connected sensors. A signal converter (AIR1-SK) must be used if more than 3 sensors are to be
connected. The sensor with the highest ventilation requirement determines the ventilation operation mode.
Ventilation
Hysteresis
window
High
stage
Low stage
or minimal
ventilation
Start: Activation
low stage
• Reduced: Activation of ventilation stage "reduced"
• Boost: Activation of ventilation stage "boost"
• Diff: hysteresis
VOD stop time: As soon as the ventilation unit has been operating at the "boost" ventilation stage for longer than 2
hours, the sensor-controlled operation will stop for the set overrun time. 0 hours means that the sensor-controlled
operation will not stop due to a high sensor requirement.
→ Timer VOD
Timer recirculation
Holiday
Overrun
Timer VOD
Monday
Per 1: XX:XX – XX:XX
Per 2: XX:XX – XX:XX
4�1�4 Recirculation
All extract air is returned to the supply air in recirculation mode.
A separate temperature setpoint and fan offset are available in recirculation mode.
The commissioning assistant must first be activated in order to use the ventilation mode.
Settings for the ventilation mode:
• Log on as User or Admin
• Call up the "Temperature" menu
• Set the setpoint (temperature) for recirculation
• Set supply air fan offset (deviation)
→ Temperature
Fan control
Timer
Access rights
OK
OK
Hysteresis
window
CO2 / VOC / relative
humidity measurement
Activation
high stage
OK
OK
58
OK
OK
V · m
OK
OK
EN
/h
3