Helios AIR1 XH 1000-8500 Notice De Montage Et D'entretien page 119

Table des Matières

Publicité

Installation and Operating Instructions
Central ventilation units AIR1 XH
conditions. This function is used to conserve energy.
The room temperature setpoint is compensated for depending on the outdoor temperature using a control curve with
8 points.
Example:
Outdoor temp . [°C]
-20
-15
-10
-5
0
5
10
15
Temp. control mode
Outd comp room
If cascade control
Max/Min supply setp
Max: XX.X °C
Min: XX.X °C
Outdoor comp setp
-20.0 °C = 25.0 °C
-15.0 °C = 24.0 °C
-10.0 °C = 23.0 °C
Outdoor comp setp
-5.0 °C = 23.0 °C
-0.0 °C = 22.0 °C
-0.0 °C = 20.0 °C
Outdoor comp setp
10.0 °C = 18.0 °C
15.0 °C = 18.0 °C
h . Outdoor Temperature Dependent Extract Air Control
The extract air temperature can be adapted when the outside temperature rises. For example, a slightly higher extract
air temperature may be acceptable at higher outside temperatures, or a slightly lower extract air temperature in cooler
weather conditions. This function is used to conserve energy.
Temp. control mode
Outd comp extr air
If cascade control
Max/Min supply setp
Max: XX.X °C
Min: XX.X °C
Outdoor comp setp
-20.0 °C = 25.0 °C
-15.0 °C = 24.0 °C
-10.0 °C = 23.0 °C
Outdoor comp setp
-5.0 °C = 23.0 °C
-0.0 °C = 22.0 °C
-0.0 °C = 20.0 °C
Room temp . [°C]
18
18
20
22
23
23
24
25
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
40
EN
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK

Publicité

Table des Matières
loading

Table des Matières