General Data Specific To The Devices Approved By Csa; Electrical Data - Burkert 1062 Manuel D'utilisation

Masquer les pouces Voir aussi pour 1062:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Version with double
inductive switch (4-wire)
• statuses detected
• valve open and valve closed
• valve open or closed
• using lights and electrical signal via
indication mode
terminal block
• colour of the lights
• an orange light comes on when the
depending on the
valve opens and a red light comes on
status detected
when the valve closes
• power up light
• green
Version with double
inductive 2-wire NAMUR
switch
• statuses detected
• valve open and valve closed
• valve open or closed
• using lights and electrical signal via
indication mode
terminal block
• colour of the lights
• an orange light goes off when the
depending on the
valve opens and a red light goes off
status detected
when the valve closes
6.4.3
General data specific to the devices
approved by csA
Degree of pollution
Degree 2, acc. to EN 61010-1
Installation category
Category I, acc. to EN 61010-1
Height above sea level
max. 2000 m
14
english
Type 1062
Technicaldata
Electric power
supplied by an SELV (Safety Extra Low
Voltage) source
6.4.4

electrical data

Connection cable
standard, diameter between 5 and
7 mm, max cross-section of the strand
1 mm
Mechanical contact
version (per contact)
• Power supply of
• 12-30 V AC or
devices approved by
12-48 V DC
CSA and CE
• Power supply
• 12-30 V DC or
of devices only
12-48 V DC/V AC or
approved by CE
48/110 V DC/V AC or
110/250 V DC/V AC
• Power consumption
• < 35 mA (48 V DC)
< 8 mA (220 V AC)
• Allowable load
• depending on the power supply
voltage and the type of load, inductive
or resistive: see „Table 1" next page
• Type of output
• contact normally open or normally
closed
2

Publicité

Table des Matières
loading