7.5
fitting the position feedback with
stroke limiter to a pneumatic
actuator size 100 or 125mm
note
the tightness of the actuator is not guaranteed when the
transparent cap is removed.
▶ Prevent the projection of fluids into the actuator.
the tightness of the position feedback is not guaranteed
when the cover is removed.
▶ Prevent the projection of fluids into the position feedback.
the position feedback may be damaged if a metal com-
ponent comes into contact with the electronics.
▶ Prevent contact of the electronics with a metal component (a
screwdriver, for example).
C
D
Type 1062
Assembly
Unscrew the cone point set
screw "C" from the 1062 to
unlock the duplication system "D"
using a hexagonal male spanner.
Carefully remove the duplication
system "D" from the housing of
the 1062.
Check that the seals have
been fitted and that they are
undamaged. Replace them if
necessary.
Put thread lock into the internal
thread in the duplication rod "E".
E
Unscrew the small transparent
F
cap "F" on the actuator, pre-
ferably by hand or using a sui-
G
table tool in order not to damage
it
Pump air into the actuator on a
valve which is normally closed
(function "A") or has a double
effect (function "I") so that the
actuator rod moves to the top
position.
Unscrew the visual position
feedback "G" using a hexagonal
male spanner.