! If the card is set to the stand-by mode, the min. / max. temperature memorized and any alarms will
not be saved
.
BLACKOUT ALARM
The defrost led blinking at high frequency indicates a blackout
Pushing the enter button the [bLO] label will be visualised on the display.
Pushing the enter button the maximum temperature recorded in the chamber will be
visualised on the display.
Pushing the enter button the defrost led is reset to standard operation.
The display shows [rES] after the abnormal event.
OPEN DOOR ALARM
In case of door open the display visualises the message [dA] alternating with the current visualisation whilst
the buzzer sounds the event with a beep of five seconds repeated every 10.
The alarm will reset upon the closure of the door and is registered in memory (high frequency flashing
defrost LED).
HIGH CONDENSATION TEMPERATURE ALARM
If the condensation temperature is too high, due to dirty condenser, the label [HtC] and the room temperature
alternate on the display.
The buzzer sounds.
The buzzer can be turned off by pressing the key
The visual warning signal stays on until the condensation tempertaure returns to normal range.
HIGH CONDENSATION TEMPERATURE ALARM (only on -25°C / -15°C and -22°C /+ 5°C units)
If the condensation temperature is high because the condenser is dirty, the label[ HtC] alternating with the
cell temperature will be shown on the display. A buzzer is also activated.
The buzzer can be turned off by pressing the key
The visual warning signal stays on until the condensation tempertaure returns to normal range.
CONDENSER DIRTY ALARM (only on -25°C / -15°C and -22°C /+ 5°C units)
If the condensation temperature is too high because the condenser is very dirty, the label [dCA] alternating
with the cell temperature will be shown on the display. A buzzer is also activated.
The buzzer can be turned off by pressing the key
The visual warning signal stays on until the condensation tempertaure returns to normal range.
In parallel, the operating set point of the device changes automatically to safeguard plant conditions.
The new setting remains until the condensation temperature returns within the normal range.
HIGH PRESSURE ALARM
If the refrigerating appliance pressure is above the specified limit, the label [HP] and the room temperature
alternate on the display.
The buzzer sounds.
.
.
.
25