UNIT WITH BROKEN SENSOR PROBES DURING DEFROST
Room probe error
In the event that the chamber sensor probe is broken or the respective connection has been interrupted
during the defrost phase the function will be completed normally.
The string set with the parameter "d6" and the label [E0] will be visualised alternatively on the display.
Humidity sensor Error
In the event that the humidity sensor is broken or its connection is interrupted on the display the label [E8], is
visualised; the humidity control device is automatically deactivated.
Condenser probe error
If the condenser probe is broken or the relevant connection interrupted, the display shows the label [E2].
The condenser fan keeps operating according to the value given to parameter "F8".
If the three probes are broken or disconnected, E0, E1, and E2 alternate on the display.
HIGH TEMPERATURE ALARM
If the room temperature exceeds the setpoint, the label [AH] and the temperature
reached alternate on the display.
Press up to display the duration of the event causing the alarm.
The buzzer may be silenced by pressing the button
The visual alarm signal stays on until the temperature returns within the normal range.
LOW TEMPERATURE ALARM
If the room temperature is below the setpoint, the label [AL] and the temperature
reached alternate on the display. The buzzer sounds.
Press down to display the duration of the event causing the alarm.
The buzzer may be silenced by pressing the button
The visual alarm signal stays on until the temperature returns within the normal range.
HIGH AND LOW TEMPERATURE ALARMS MEMORIZED
The defrost led blinking at high frequency indicates high or low temperature alarm.
Pushing the enter button the type of alarm recorded will be visualised on the flashing
display.
Pushing the enter button the critical temperature recorded will be visualised on the
flashing display.
Pushing the enter button the time duration of alarm event, expressed in minutes, will
be visualised on the flashing display.
Pushing the enter button the operation of the defrost LED will be reset to its normal
state.
The display shows [rES] after the abnormal event.
In the event that another alarm event were to occur, for high or low temperature, if the information relative to the
preceding anomaly hasn't been visualised by the operator, this latter will be overwritten by the more recent data.
If the high temperature alarm is on, the compressor keeps working; if the low temperature alarm is on, the
compressor stops.