Press the on/sby/enter key to confirm your selection.
Use the keys up and down to select the new value
Press the on/sby/enter key to confirm your selection.
USER PARAMETER CONFIGURATION - PROBE READING
Push the up and down buttons simultaneously and hold down for more than 3
seconds.
The label [Loc] is visualised.
Utilise the up and down buttons to scroll the sensor probe readings and the user
parameters.
Press the on/sby/enter key to confirm your selection and enter the mode for reading
probes or changing parameters.
The current value blinks on the display.
Use the keys
Press the on/sby/enter key to exit or confirm the selection of the parameter new
value; the setting stops blinking.
Information accessible to qualified staff only.
On starting the appliance, a "LAMPTEST" phase will start.
If you press the on/sby/enter key 3 times consecutively during this phase, all default
parameters will be reset.
The display shows [rLd] indicating the reset of the values pre-set by the
manufacturer.
ATTENTION: the default values in memory refer to the configurations (tn, bts, btv) exclusively.
UNIT WITH BROKEN SENSOR PROBES DURING CONSERVATION
Room probe error
If the room probe is broken or the relevant connection interrupted, the display shows the label [E0].
The appliance keeps operating in storing according to the values given to parameters C5 and C6.
The inner fan keeps operating according to the value given to "F3"
Evaporator fan error (only on -22°C / +5°C units)
If the room probe is broken or the relevant connection interrupted, the display shows the label [E1].
to select the new value, applicable to parameters only.
DEFAULT PARAMETER RECOVERY
ALARMS
15