Connecting The Condensed Water Drain For The Tscs 12Xx And Ts 12Xx Models; Connecting The Condensed Water Drain Of The Indoor Unit - Tectro TS 1225 Manuel D'installation

Masquer les pouces Voir aussi pour TS 1225:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 32
Outside-
diameter
Ø 6.35
Ø 9.53
Ø 12.7
Ø 16.0
e.
Insulate the fittings on the indoor unit with insulation to prevent condensed water leakage.
f.
Wrap the piping, connecting cable and outlet hose, situated behind the indoor unit, with tape into
a solid bundle. This will make the mounting of the indoor unit to the mounting plate easier.
Indoor unit
Connecting
cable
Picture 14
G
ATTENTION
Cupper piping must be insulated separately.
G
ATTENTION
Use extreme caution when bending the piping. Always assure the piping is bend and not kinked.
In case of a kinked pipe: replace the entire pipe or the kinked part because this could cause a
refrigerant leak and lead to malfunctioning of the air conditioner.
9.
CONNECTING THE CONDENSED WATER DRAIN FOR THE TSCS 12XX AND TS
12XX MODELS.
9.1

Connecting the condensed water drain of the indoor unit.

Connect the supplied condensed water hose to the indoor unit fitting by sliding the condensed water hose
over the grommet of the hose of the indoor unit. Ensure that the height of any section of the condensed
water hose isn't higher than the height of the drain outlet and don't place the end of the hose in the water.
See Fig. 15.
Always direct the condensed water hose under the refrigerant piping, this prevents overflow of the con-
densed water container.
4
84
Torque
Extra torque
(N.cm)
(N.cm)
1500
(153 kgf.cm)
(163 kgf.cm)
2500
(255 kgf.cm)
(265 kgf.cm)
3500
(357 kgf.cm)
(367 kgf.cm)
4500
(459 kgf.cm)
(479 kgf.cm)
Wrapping tape
Piping
Drain hose
1600
2600
3600
4700

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Tscs 1225Ts 1232Tscs 1232Ts 1248Tscs 1248

Table des Matières