9.
CONNECTING THE CONDENSED WATER DRAIN FOR THE TSCS 8XX- 10XX AND
TS 8XX MODELS.
9.1

Connecting the condensed water drain of the indoor unit.

Connect the supplied condensed water hose to the indoor unit fitting by sliding the condensed water hose
over the grommet of the hose of the indoor unit. Ensure that the height of any section of the condensed
water hose isn't higher than the height of the drain outlet and don't place the end of the hose in the water.
See Fig. 15.
Always direct the condensed water hose under the refrigerant piping, this prevents overflow of the con-
densed water container.
WARNING
• Make sure the drain hose is situated at the bottom of the pipe bundle. Positioning the hose at
the top side can cause overflow of the condensed water container.
• Let the drain hose slope slightly over the entire length so the condensed water can be
evacuated smoothly.
Picture 15
9.2

Connecting the condensed water drain of the outdoor unit.

Place the sealing ring on the drainage pipe and position the drain connector in the hole on the bottom side
of the outside unit. Connect the drainage pipe to a drain hose (not supplied). In this way the condensed
water that is accumulated in the heating mode of the air conditioning can be drained. See Fig. 16.
Picture 16
4
56

10. ELECTRICAL INSTALLATION

Use a separate circuit for the air conditioner. Ensure the circuit is protected by a suitable fuse. See
table below.
The supply voltage must be within 95%~105% of the rated voltage, which is specified on the rating
label.
The supply circuit must be protected by an earth-leakage circuit breaker.
Ensure that the air conditioning is properly grounded.
Connect the cables according the wiring diagram. See Chapter 11.
All wiring has to comply with national and local electrical standards and regulations and has to be
connected by qualified technicians.
Model
Mains
220 - 240V, ~50Hz
≤ 3,5 kW
> 3,5 kW
220 - 240V, ~50Hz
G
ATTENTION!
The supply voltage must be according the rated voltage of the air conditioning

11. CONNECTING THE POWER CABLES

11.1 Connecting the power cables for the TSCS 8xx- 10xx models.

a.
A power cable with a length of 4.0 meter for the electrical connection between indoor and outdoor
unit is supplied with the device and can be found in the packaging of the refrigerant piping (indoor
unit).
b.
This electrical cable is supplied with an electrical push fit coupling.
c.
This electrical cable is supplied with an electrical push fit coupling.
d.
Remove the cover plate of the terminal block of the outdoor unit by unscrewing the screw.
e.
Click the connector of the indoor unit into the connector of the outdoor unit and secure the cable
on the connector block with the mounted cable clamp.
Cover plate
Picture 17
f.
Connect the power cable only when the entire installation of the air conditioner is completed.
Rated input current
Diameter power cord
(switch/fuse)
16A
2,5 mm
2
16A slow
2,5 mm
2
4
57