Protection Of The Connection To The Consumption Grid; Protection Of The Connection To The Auxiliary Grid/Genset - Ingeteam INGECON SUN STORAGE 1Play Série Manuel D'installation

Masquer les pouces Voir aussi pour INGECON SUN STORAGE 1Play Série:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 155
Ingeteam

6.4. Protection of the connection to the consumption grid

Thermomagnetic circuit breaker
It is possible to install a thermomagnetic circuit breaker and/or fuse on the connection between the inverter and
the consumption grid.
The following table provides the necessary data for the selection of these devices by the installer.
INGECON SUN STORAGE 1PLAy
You must take into account when selecting the protection that the ambient working temperature influences the
maximum current permitted by these protections as indicated by the manufacturer.
Residual current device
You must comply with applicable regulations governing the protection of people in the consumption grid.

6.5. Protection of the connection to the auxiliary grid/genset

It is possible to install a thermomagnetic circuit breaker and/or fuse on the connection between the inverter and
the auxiliary grid/genset.
The following table provides the necessary data for the selection of these devices by the installer.
INGECON SUN STORAGE 1PLAy
70
3 / 3TL
6 / 6TL
3 / 3TL
6 / 6TL
Maximum inverter
current
13 A
26 A
Maximum auxiliary
grid/genset current
50 A
50 A
ABH2013IQM01_A - Installation and Operation Manual
Preparation for installing the unit
Rated current for the
type-B thermomagnetic
circuit breaker
20 A
32 A
Rated current for the
type-B thermomagnetic
circuit breaker
63 A
63 A

Publicité

Table des Matières
loading

Table des Matières