Technical Data - Wilo Yonos PARA High Flow Série Notice De Montage Et De Mise En Service

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 49
5.2

Technical data

Max. flow rate
Max. delivery head
speed
Mains voltage
Frequency
Rated current
Energy Efficiency Index (EEI)
Insulation class
Protection class
Power consumption P
Nominal diameters
Connection flanges
Pump weight
Permissible ambient temperature
Permissible fluid temperature
Temperature class
Max. rel. humidity
Degree of pollution
Max. permissible operating
pressure
Approved fluids
Wilo- Yonos PARA Hig Flow
Emission sound-pressure level
Residual current ΔI
Electromagnetic compatibility
1)
The pump is equipped with a power limiting function which provides protection against overload.
This can have an effect on the output depending on operation.
2)
See the following warning
Installation and operating instructions Wilo-Yonos PARA High Flow
depends on the pump type, see catalogue
depends on the pump type, see catalogue
depends on the pump type, see catalogue
1~230 V ±10% in acc. with DIN IEC 60038
50/60 Hz
see rating plate
see rating plate
see rating plate
see rating plate
see rating plate
1
see type key
see type key
depends on the pump type, see catalogue
-20°C to +40°C
-20°C to +110°C
TF110
≤ 95%
2 (IEC 60664-1)
see rating plate
Heating water (in acc. with VDI 2035/VdTÜV Tch 1466)
water/glycol mixtures, max. mixing ratio 1:1 (for mixtures with
glycol the conveying data of the pump should be corrected to
those for the higher viscosity, depending on the percentage
mixing ratio)
Only use brand-name goods with corrosion protection inhibi-
tors; comply with the manufacturer's specifications and safety
data sheets.
The pump manufacturer's approval must be obtained for the
use of other fluids.
Ethylene/propylene glycol with corrosion inhibitors.
No oxygen binders, no chemical sealants (pay attention to sys-
tem sealed with regard to corrosion technology according to VDI
2035; leaks must be reworked).
Commercially available anti-corrosion agents
without anodic inhibitors with a corrosive effect (e.g. under-
dosing due to consumption).
Commercially available combination products
without inorganic or polymer film formers
Commercially available cooling brines
< 52 dB(A) (depending on the pump type)
≤ 3.5 mA (see also section 7.2)
Emitted interference in acc. with:
EN 61800-3:2004+A1:2012 / Residential (C1)
Interference resistance in acc. with
EN 61800-3:2004+A1:2012 / Industrial (C2)
1)
1)
2)
2)
2)
English
25

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Yonos para hf 25/12

Table des Matières