Technical data

Refer to the catalogue for details on pump selection.
NOTICE
Wilo-ClimaForm cold water insulation shells do not replace standard Wilo-Stratos
MAXO series thermal insulation shells.
6
Technical data
Technical data
Material
Field of application
Steam diffusion resistance µ
Flame protection
Thermal conductivity
Permitted relative humidity
Guidelines
Table 1: Technical data
7

Scope of delivery

ƒ
ƒ
ƒ
ƒ
NOTICE
The processing materials required for the Armacell system (e.g. Armaflex special
cleaners, Armaflex 520 adhesive) must be provided by the customer.
Installation and operating instructions Wilo-ClimaForm
Wilo-ClimaForm cold water insulation shell
Armaflex strip (seal between cold water insulation shell and motor flange on the
pump housing)
Armaflex tape (strip to stick over the adhesive seam of both halves of the mould
below the condensate drainage outlet of the motor housing)
Installation instructions
Elastomer insulation material, AF/Armaflex
system made by Armacell
Permissible fluid temperature:
-10 °C to +110 °C
Ambient temperature:
-10 °C to +40 °C
≥ 10,000
Flame retardant, B-s3, d0 (as per
EN 13501-1),
free from flame-retardant agent (HBCD)
0.033 W/(m·K)
70 %
Compliant with RoHS and REACH