Loosen the screws of the mechanical stops, then move it in front of the carriage, as shown on figure 14. Firmly push the carriage in the
closing direction and, once reached the position, tighten the screws (A) fully down (figure 15).
12_
For opening phase, use any available mechanical stop, both the door one and the complete automation track are equally fine.
13_
Attempt to move the door manually. Ensure that the carriage slides freely, without friction on the guide, and that manual manoeuvres
are smooth without requiring particular effort.
2.5 Installation of various devices
To install the other devices envisaged, refer to the relevant instructions. Check in figure 3 the devices that can be connected to T-SKY.
2.6 Optional accessories
The range of T-SKY motors can be completed with the following optional accessories:
150SETSKY external manual release for application on handle;
100BANT (fig. 17)
Adaptor for up-and-over doors 100BANT must be used to power operate coun-
terweight up-and-over doors with drive models T-SKY and T-SKY1.
• 750BATTSKY Battery pack (see relative instructions).
2.7 Electrical connections
All electrical connections must be made withthe system disconnected from the power supply.
1_
To open the protection cover and access the electronic control unit of T-SKY, press on the side of the cover and turn the panel door as
shown in fig. 18.
2_
Route the connection cables to the various devices through the cable clamps, leaving a length 20÷30cm more than necessary. See para.
1.2 for the type of cables and figure 3 for connections.
3_
Make the connections as shown in the diagram in figure 19. Terminals are removable to facilitate connections.
2.8 Connecting to the power supply
For electric power supply of T-SKY simply connect the 230 Vac line to the transformer safety fuse holder (fig. 19).
T-SKY must be connected to the power mains by skilled and qualified personnel, in possession of all requirements for full
compliance with all legal provisions, standards and regulations.
The electric power line must be protectedagainst short circuits and dispersion to earth; a device must be fitted to enable
shutoff of the power supply during installation or maintenance of T-SKY.
3. K691M ELECTRONIC BOARD
3.1 Technical specifications
Board power supply
Max. DC motor power
Quick-acting motor protection fuse
(F1 - 5x20)
Quick-acting battery protection fuse
(F2 - 5x20)
Quick-acting 24 Vdc auxiliary circuit
protection fuse (F3 - 5x20)
Motor power circuit supply voltage
Auxiliary device circuit power supply volt-
age
Logic circuit power supply voltage
Operating temperature
Housing protection rating
3.3 Terminal board connections
FS1 - FS2
24 Vac board power supply input – Powered by transformer in relative compartment of T-SKY motor and protected by fuse (F 6,3A)
on the 230 Vac power line.
1-4
(Photocell) PHOTOCELL OR SAFETY DEVICE input active on closure (Normally Closed contact); when activated, during the closing phase,
generates a door stop command followed by complete door re-opening; in the opening phase generates a temporary stop command
until the detected obstacle is removed (only if dip switch nr. 3 is set to ON). In the case of multiple safety devices, connect all NC contacts
IN SERIES. 1= PHOTOCELL .
N.B.
The photocell transmitter must always be powered by terminals 5 and 6, as the safety system check is performed on the latter
(Fototest).
To disable the safety system test function, or when using the photocells, set dipswitch 6 to OFF. If the fototest function fails,
there is a control unit fault.
2-4
(Stop) STOP button input (Normally Closed contact); stops the door at any point of travel, temporarily inhibiting automatic closure, if
programmed. It resumes operation when the OPEN/CLOSE button is pressed or radio control is used. 2= STOP, 4= COMMON
3-4
(Open/Close) OPEN/CLOSE button input (Normally Open contact); activates door opening and closing and is controlled by operation of
dipswitches 2 and 4. 3= OPEN/CLOSE.
5-6
(Photocell TX) 24 Vdc output, for PHOTOCELL TX POWER SUPPLY (only those that perform the Fototest function) max. nr. 1 photocell
3.2 Diagnostics leds
DL1 (OPEN/CLOSE)
24V AC - 50 Hz
50 W - 24V DC
DL2 (STOP)
F 10 A
DL4 (PHOTO)
DL3 (ERR)
F 10 A
DL5 (POWER)
T 2A
24V DC
24V DC
5V DC
-20 °C ÷ +55 °C
IP 30
27
• 100BINSUPP33 (fig. 3) Additional Ceiling Fixing Kit.
• 100PROC33 (fig. 8) Extension for T-SKY with chain.
• 100PROB33 (fig. 9) Extension for T-SKY with belt.
red led indicating use of OPEN/CLOSE
button
green led indicating use of STOP but-
ton
green led indicating PHOTOCELL
red led indicating ERRORS
green led indicating POWER ON
(also when battery powered)